Electromagnetic Compatibility 
MICROMASTER  Applications Handbook 
31 
6.2.2 EMC 
Guidelines 
The guidelines for installation and wiring are detailed in the Operating Instructions, 
but the key points are as follows: 
1. 
Ensure all equipment in the cubicle is well earthed, using thick, short earthing 
cable.  Earth control equipment in the same way to the same earth point.  Star 
point grounding, shown in Figure 6-2, is ideal, but a solid busbar is acceptable 
provided it is well grounded. 
 
Monitor
System
PLC
Inverter
Thick, short, grounding cable
connected to common ground point
 
Figure 6-2 
Star Point Grounding 
2.  
Use screened leads for connections to the control circuitry.  Ground the screen at 
both ends. 
PLC
Inverter
 
Figure 6-3 
Screening of Control Cables 
3.
 
Separate the control cables from the power connections (e.g. supply and motor 
connections) as much as possible, using separate trunking etc. 
 
MM
MM
Input (Supply) Connections
Output (Motor) Connections
Control Connections
 
Figure 6-4 
Separation of Control and Power Connections