2  Installation
MICROMASTER 410    Operating Instructions
6SE6400-5EA00-0BP0
19
2.2 Power 
Losses
Figure 2-2 shows the power loss for
the MICROMASTER 410 Inverter.
The graph can be used to read the
loss at full load of a particular variant.
2.3 
Ambient operating conditions
Temperature
Frame Size
AA
AB
Min. [
°°°°
C]
-10
-10
Max. [
°°°°
C]
50
50
For UL compliance the maximum surrounding air temperature for 750 W inverters
is 40 ºC and 50 ºC for all other inverters.
Humidity Range
Relative air humidity 
 95 % Non-condensing
Altitude 
If the inverter is to be installed at an altitude > 1000 m or > 2000 m above sea
level, derating will be required.
Figure 2-3 below shows the permissible rated input voltages and output current for
inverter installations from 500 m to 4000 m above sea level.
Permissible rated input voltage
as a percentage of the nominal voltage
100
90
80
60
70
1000
2000
3000
4000
500
500
Installation altitude in metres above sea level
Permissible rated output current
as a percentage of the nominal current
100
90
80
60
70
1000
2000
3000
4000
In
p
u
t vo
lt
a
g
e
Ra
te
d out
pu
t c
u
rre
nt
Figure 2-3
Derating for Altitude
230V MM410 Power losses
0
10
20
30
40
50
60
70
80
0,12
0,25
0,37
0,55
0,75
Power output kW
P
o
wer l
o
sses W
Figure 2-2
Power Losses, 230 V