Manual Supplement 
00809-0500-4530, Rev AA
October 2010
1-33
Rosemount 5300/5400 Series
ScadaPack
Figure 1-14. Wiring Diagram for 
Connecting 5300/5400 Modbus to 
SCADAPack 32
Table 1-24.  Parameter Values (in 
case of SCADAPack 32)
The Input Register Base Number needs to be added to the Input Register 
address of the 5300/5400 transmitter. In this case, register 1302 needs to 
have 31303 entered as the address etc.
Kimray DACC 2000/3000
This table shows input types in Kimray IMI software and the corresponding 
value. The communication port must be configured to use “Tank Levels” 
protocol.
Table 1-25.  Kimray Input Types and 
Corresponding Values
RS-485 on COM1
1 +5 V
2 RX-
3 TX-
4 GND
5 RX+
6 TX+
7 Not Used
8 Not Used
SCADAPack32
MA
MB
POWER +
POWER -
5300/5400 Modbus
Power Supply
+ 8 to + 30 Vdc 
(max. rating)
REF
Parameter
Value
Baud Rate
9600
Floating Point Format Code
0
RTU Data Type
Floating Point
Input Register Base Number
30001
Kimray Inp type
5300/5400 variable
Format
Tank Level1
PV
ddd.dd.alt. -dd.dd
Tank Level2
SV
ddd.dd.alt -dd.dd