GE 90-30/20/Micro Manual De Usuario
3-18
Series 90-30/20/Micro Programmable Controllers Reference Manual
–
September 1998
GFK-0467K
3
Addition of I/O Module
The Fault Category Addition of I/O Module applies to Model 30 discrete and analog I/O modules.
There are no fault types or fault descriptions associated with this category. The fault action is
Diagnostic.
There are no fault types or fault descriptions associated with this category. The fault action is
Diagnostic.
Description:
The PLC operating software generates this error when an I/O module which had
been faulted returns to operation.
been faulted returns to operation.
Correction:
(1)
No action necessary if the module was removed or replaced,
or the remote rack was power cycled.
or the remote rack was power cycled.
(2)
Update the configuration file or remove the module.
Description:
The PLC operating software generates this error when it detects a Model 30 I/O
module in a slot which the configuration file indicates should be empty.
module in a slot which the configuration file indicates should be empty.
Correction:
(1)
Remove the module. (It may be in the wrong slot.)
(2)
Update and restore the configuration file to include the extra
module.
module.