GE 90-30/20/Micro Manual De Usuario

Descargar
Página de 311
3-18
Series 90-30/20/Micro Programmable Controllers Reference Manual
 
 
September 1998
GFK-0467K
3
Addition of I/O Module   
The Fault Category Addition of I/O Module applies to Model 30 discrete and analog I/O modules.
There are no fault types or fault descriptions associated with this category. The fault action is
Diagnostic.
Description:
The PLC operating software generates this error when an I/O module which had
been faulted returns to operation.
Correction:
(1)
No action necessary if the module was removed or replaced,
or the remote rack was power cycled.
(2)
Update the configuration file or remove the module.
Description:
The PLC operating software generates this error when it detects a Model 30 I/O
module in a slot which the configuration file indicates should be empty.
Correction:
(1)
Remove the module. (It may be in the wrong slot.)
(2)
Update and restore the configuration file to include the extra
module.