Section 2: Timers and Counters
This section explains how to use on-delay and stopwatch-type timers, up counters, and down
counters. The data associated with these functions is retentive through power cycles.
counters. The data associated with these functions is retentive through power cycles.
Abbreviation
Function
Page
ONDTR
Retentive On-Delay Timer
4-11
TMR
Simple On-Delay Timer
4-14
OFDT
Off-Delay Timer
4-17
UPCTR
Up Counter
4-20
DNCTR
Down Counter
4-22
Function Block Data Required for Timers and Counters
Each timer or counter uses three words (registers) of %R memory to store the following
information:
information:
current value (CV)
word 1
preset value (PV)
word 2
control word
word 3
When you enter a timer or counter, you must enter a beginning address for these three words
(registers) directly below the graphic representing the function. For example:
(registers) directly below the graphic representing the function. For example:
(enable) *|ONDTR|*(Q)
time
(reset)
-
R
(preset value)
-
PV
(address)
-
Enter the beginning address here.
here.
-
ONDTR
-
Note
Do not use consecutive registers for the 3 word timer/counter blocks. Logicmaster
does not check or warn you if register blocks overlap. Timers and counters will
not work if you place the current value of a block on top of the preset for the
previous block.
does not check or warn you if register blocks overlap. Timers and counters will
not work if you place the current value of a block on top of the preset for the
previous block.