Page H-96
SITRANS LR 460 (PROFIBUS PA) – INSTRUCTION MANUAL 
7ML19985JM01
mmmmm
H
: C
o
mmuni
ca
ti
on P
A
AIFB1 and AIFB2 return 5 bytes of data each:
The first 4 bytes are the floating point representation (IEEE) of the variable. The variables 
are the outputs of the function block. The 5th byte is the status word and the list of 
possible values is given in the chart below. 
The 5 bytes must be read consistently, in a contiguous chunk: they cannot be read byte by 
byte, and cannot suffer an interrupt. If you are using an S7-300 / 400, you will need to use 
SFC14 DPRD_DAT: Read Consistent Data of a Standard PD Slave.
Status Byte
Status Codes for Good Quality
Values in hex notation
Description 
0x80
Data is GOOD.
0x84
A parameter in the function block has been changed: status 
active for 10 s
0x89
Active low warning.
0x8A
Active high warning.
0x8D
Active low alarm.
0x8E
Active high alarm.
Status Codes for Bad Quality
Values in hex notation
Description 
0x10
This could be caused by LOE or by a sensor malfunc-
tion: value is BAD.
0x01
There is an error in the configuration of the function 
blocks in PROFIBUS PA
a
a.
This could happen when a firmware download has been done, but a system 
reset has not been done. This could also happen if the function blocks are not 
configured properly using PDM or acyclic services.
0X1F
The function block has been placed out of service. 
(You will see this only if you read status word via 
acyclic services, after placing the function block out of 
service.)
0xC4
Bad configuration: value is BAD.
0XDE
AI block out of service: value is BAD.
Floating Point
Status
AIFB2
AIFB1
byte 1
byte 2
byte 3
byte 4
byte 5
byte 6
byte 7
byte 8
byte 9
byte10
byte10