SITRANS LR 460 – INSTRUCTION MANUAL 
7ML19985JM01
mmmmm
In
st
a
lla
ti
o
n
Installation
Mounting Location
WARNINGS: 
SITRANS LR 460 is to be used only in the manner outlined in this 
manual, otherwise protection provided by the equipment may be 
impaired.
Installation shall only be performed by qualified personnel and in 
accordance with local governing regulations.
Notes: 
• For European Union and member countries, installation must be according to ETSI 
EN 302372.
• Refer to device nameplate for approval information. 
• Use appropriate conduit and conduit fittings or cable glands, to maintain IP or NEMA 
rating.
• Observe all maximum permissible ambient and process temperatures. Refer to 
• For US and Canadian installations, see 
Notes:
• Provide easy access for viewing the display and programming via the handheld 
programmer.
• Provide an environment suitable to the housing rating and materials of construction.
• Provide a sun shield if the device is mounted in direct sunlight.
ambient temperature 
max. 65 °C (149 °F)-
process temperature 
max. 200 °C (392 °F)
flange 
temperature