SITRANS LR 460 – INSTRUCTION MANUAL
7ML19985JM01
mmmmm
Pa
ra
m
e
te
rs
4.3.4. Min Limit
The mA value to correspond with 4.1.7.1. Lower Value .
4.3.5. Max Limit
The mA value to correspond with 4.1.7.2. Upper Value .
4.3.6. FS Mode 
The mA value to be output in the event of a fault or failure.
4.3.7. FS Value 
A user-defined mA value to be reported when the Fail-safe timer expires.
4.3.8.  4 mA Trim
Calibrates the 4 mA output.
a. Set 
 to MANUAL mode.
b. Set 
 to 4 mA.
c. Attach a calibrated meter and check the output at the terminals. Record the 
remote reading in mA.
d. Enter the recorded value in 
.
e. Restor
 to its previous setting.
f. Confirm that the mA output is as expected.
Values
Range: 
Default: 3.8 mA
Values
Range: 
Default: 20.5 mA
 Options
mA HOLD
* Level remains at last reading.
mA SET
User-defined value set in 
mA HIGH
Use Max Limit as material level.
mA LOW
Use Min Limit as material level.
Values
Range: 3.5 to 20.5 mA
Default: 3.5 mA
Values
Range: 2.0 to 6.0 mA
Related parame-
ters
 A mA value derived from the ratio of current level to the range 
between Lower Value and Upper Value.