SITRANS LC 500 – INSTRUCTION MANUAL 
 7ML19985GE01
mmm
mm
Inst
allat
ion
SITRANS LC 500: Installation
Handling Electrodes
Notes:
• Installation shall only be performed by qualified personnel and in accordance with 
local governing regulations.
• This product is susceptible to electrostatic discharge. Follow proper grounding 
procedures.
 WARNINGS: 
• Disconnect the device before any welding is carried out in the vicinity 
of the instrument. 
• Provide protection when the solid-state switch is activating an 
external relay to prevent possible switch/relay damage resulting from 
inductive spikes generated by the relay coil. (See 
 WARNINGS:
• Do not scratch or gouge the PFA electrode insulation since this could 
reduce the integrity of the insulation and the useful life of the 
electrode.
• Be careful with an enamel-insulated electrode
1
• Do not damage the insulation jacket on the electrode during shipping, 
packing, and installation
2
. Any damage to the electrode can prevent 
proper performance.
• (ATEX 100): Precautions MUST be taken to avoid ignition due to 
hazardous electrostatic discharges:
a. Where an isolated probe is used in gas, vapor, or a non-
conductive liquid that is potentially explosive, requiring 
apparatus group IIC equipment.
b.  Where the probe is used in a potentially explosive dusty 
atmosphere.
1.
Normally the enamel insulation is protected by a stilling well, which is part of 
the design.
2.
Most electrodes use PFA insulation, a very dense and reliable type of Teflon® 
that prevents leakage and corrosion of the metal electrode and acts as an 
insulator when conductive materials are being measured.