Siemens LC 500 Manual De Usuario
Page 88
SITRANS LC 500 – INSTRUCTION MANUAL
7ML19985GE01
mmm
mm
Appendix E
Interface Version
Designed specifically for interface level where a long distance active shield portion of the
electrode is required (up to 35 meters) before the measurement portion of the electrode
begins. Common in large storage tanks for oil where the bottom of the tank invariably has
a layer of water below the oil. Often, when measurement spans as much as 5.5 meters
(for the water), up to 35 meters of flexible bellows cable are used.
electrode is required (up to 35 meters) before the measurement portion of the electrode
begins. Common in large storage tanks for oil where the bottom of the tank invariably has
a layer of water below the oil. Often, when measurement spans as much as 5.5 meters
(for the water), up to 35 meters of flexible bellows cable are used.
Interface Version, threaded (optional sanitary and flanged)
Process Connection Size
•
threaded version: ¾", 1",
1½", 2" NPT, BSPT, or JIS
1½", 2" NPT, BSPT, or JIS
•
sanitary version: on
customer request
customer request
•
flanged version: on
customer request
customer request
Options
•
thermal isolator
•
stilling well
Aluminum Enclosure
•
NEMA 4 / Type 4 / IP65
Conduit Entry:
•
½" NPT (2x)
ø 160 mm
(6.3”)
transmitter
enclosure
enclosure
seal gland
process
connection:
flange or
threaded
mounting
connection:
flange or
threaded
mounting
flexible tube
probe
ø 16 mm (0.63”) or
ø 24 mm (0.94”)
ø 24 mm (0.94”)
185 mm (7.28”)
insertion length
35 m (115 ft) max.
Active Shield
active
length
ø16 mm=2 m
ø24 mm=5.5 m
adjustable
extension
extension
dependent on
extension length
extension length
100 mm (3.9”)
inactive tip