Honeywell MRP-2001E Manual De Usuario

Descargar
Página de 136
Output Circuits
Installation
MRP-2001 & MRP-2001E   PN 53040:A  4/16/2007
23
2.4 Output Circuits
2.4.1 Outputs/Notification Appliance/Releasing Circuits
Each of the four Style Y (Class B) Notification Appliance Circuits can output a maximum of 3.0 
amps of current.  Total current drawn from these as well as other DC power outputs cannot exceed  
7.0 amps (refer to battery calculations section). Each circuit is supervised, power-limited and 
provides special application power.  Refer to the Device Compatibility Document for a listing of 
compatible notification appliances.
The NACs can be converted to Style Z (Class A) by installing two optional Class A Converter 
module.  Refer to  "CAC-5X Class A Converter Module" on page 26.
Figure 2.7 NAC/Output Connections
Class B Notification Appliance Circuits (supervised and power-limited)
4.7 K
Ω
, ½ watt resistor P/N:71252
Dummy load any unused 
circuits (P/N: 71245)
Polarized Bell
Polarized Strobe
Polarized Horn
Polarized Horn
Polarized Bell
Notification Appliance Circuits 
polarity shown in alarm condition
rp2001nac
.cdr
Releasing Solenoid
Polarized Strobe
+    -   +     -
+    -   +     -
Note: Short Circuit Supervision must be enabled when using the 
REL-4.7K for Canadian Applications.  Refer to the section titled 
 "Release Circuit 1 or Release Circuit 2" on page 58 for information 
on enabling short circuit supervision.
Ferrite Bead in open position
Ferrite Bead in closed position
Large gauge wire 
should be looped 
through bead at least 
once as illustrated.  
Smaller gauge wire can 
be looped more often.
Ferrite Bead (P/N 29150)
Ferrite Bead
P/N 29150
Ferrite Beads
P/N 29150