Installation
Installation of Optional Modules
28
MRP-2001 & MRP-2001E   PN 53040:A  4/16/2007
2.6.2 4XTMF Municipal Box Transmitter Option Module
The  4XTMF module can be plugged into connectors J4 and J5 on the main circuit board.
The following steps must be followed when installing the 4XTMF module:
1. Remove all power (AC and DC) from the FACP before installing the modules
2. Cut jumper JP30 on the main circuit board to allow the control panel to supervise the 
placement of the 4XTMF option module
3. Install the two supplied metal standoffs in the locations indicated.  These standoffs provide 
the required earth ground protection
4. Carefully plug the connectors on the option module into connectors J4 and J5 on the FACP 
main circuit board, being careful not to bend any pins 
5. Secure the option module to the standoff on the main circuit board with the supplied screws
6. When the installation has been completed, connect the wiring to the modules as indicated in 
the following sections
7. Test system for proper operation
Figure 2.13 4XTMF Option Module Connection
J4
J5
Standoffs
rp2001bord.cdr