Programming
Master Programming Level
60
MRP-2001 & MRP-2001E   PN 53040:A  4/16/2007
3.5.3.4 Auto Silence
The Auto Silence feature, when enabled, automatically silences all main circuit board 
silenceable notification appliances after a programmed length of time.  To enable this feature 
and program the time delay before Auto Silence activation, press 2 while viewing Output 
Screen #2.  The following screens will be displayed:
To disable the Auto Silence feature, press 1 for No while viewing Auto Silence Screen #1.  To 
enable the Auto Silence feature, press the number corresponding to the time delay which will 
elapse before Auto Silence activates.  This information will be stored in memory and the 
display will return to NAC Screen #1.
Note:  If the Output Circuit has been programmed as a Releasing Circuit, the Auto Silence 
Option will not be available and the display will indicate N/A next to it.
3.5.3.5 Silence Inhibited
The Silence Inhibit feature, when enabled, prevents the silencing of the selected main circuit 
board Output for a period of one minute.  Resetting the FACP will also be prevented for one 
minute while the Output programmed for silence inhibit is activated.  Pressing 3 while viewing 
Output Screen #2 will cause a screen to be displayed with the options 1=No Silence Inhibit and 
2=1 Min. Silence Inhibit.  Pressing 1 will disable the Silence Inhibit feature while pressing 2 
will enable a 1 minute Silence Inhibit for the selected Output.
  AUTO SILENCE
1=NO
2=5 MINUTES
3=10 MINUTES
Auto Silence Screen  #1  
  AUTO SILENCE
1=30 MINUTES
Auto Silence Screen #2  
  AUTO SILENCE
1=15 MINUTES
2=20 MINUTES
3=25 MINUTES
Auto Silence Screen #3  
     OUTPUT #
1=SILENCEABLE  YES
2=AUTO SILENCE  NO
3=SIL INHIBITED NO
Output Screen #2