Exhaust System Maintenance
The dryer interior and the complete exhaust system 
should be inspected after one year of use and cleaned 
if necessary. Inspect and clean exhaust duct every one 
to two years as required thereafter. The weather hood 
should be checked frequently to make sure the 
dampers move freely, dampers are not pushed in and 
that nothing has been set against them. This 
maintenance work should be done by a qualified 
service person.
Exhausting the dryer in hard-to-reach locations can be 
accomplished by installing the 521P3 Flexible Metal 
Vent Kit, available as optional equipment at extra cost. 
The kit comes in two halves that can be separately 
attached to the dryer and wall outlet. Once attached, 
the dryer can be slid back into position and the two 
halves can be connected from the front.
Figure 28 
Dryer Airflow
Efficient dryer operation requires proper dryer airflow. 
Proper dryer airflow can be evaluated by measuring 
the static pressure.
Static pressure in the dryer’s exhaust duct should be no 
greater than that shown in Figure 29. (Check with 
dryer running and no load.)
NOTE:  This can be measured with a manometer 
placed on the exhaust duct approximately two feet 
(61 cm) from the dryer. Refer to Figure 29
Figure 29 
IMPORTANT: DO NOT block the airflow at the 
bottom of the dryer’s front panel with laundry, 
rugs, etc. Blockage will decrease airflow through 
the dryer, thus reducing the efficiency of the dryer.
H615I
To reduce the risk of electric shock, 
disconnect the electrical service to the dryer 
before cleaning.
W043
WARNING
D615I
521P3 FLEXIBLE METAL VENT KIT
D012I
1
Manometer
2
Exhaust Duct
DR012A-IN
1
2
MAXIMUM STATIC 
PRESSURE IN 
WATER COLUMN
0.6 inches (1.5 cm)
MEASURING STATIC PRESSURE