NOTE:
 If you attempt to learn in a device that is already learnt it will be deleted and added to 
the new zone eg: If a WPIR is in zone 3 and you wish to move it to zone 5 relearning in zone 
5 will delete it from zone 3 and add it to zone 5. 
 
TO DELETE A DETECTOR 
 
1. 
 
 
 
Set the dipswitch to on for the zone you wish to delete. I.e. if 
you wish to delete the sensor currently programmed into 
Zone 1, set dipswitch 1 to on as shown. 
 
2. 
 
 
Press the DELETE button. 
3. 
 
 
The unit will beep once to confirm the zone was deleted. 
 
Walk test mode
 should be used when testing the system or after a new detector has been 
learnt into the system. 
− 
Beeps once on entering this mode 
− 
The unit will beep out the zone number of any device triggered 
− 
The unit will not beep out if the signal strength is not good enough 
Any dipswitch, or remote pressed, will exit walk test mode. 
The detectors being tested should also be set into Walk Test Mode, see page 22. 
 
WALK TEST MODE  
 
1. 
 
 
Set dipswitches 1 and 3 to on.  
2. 
            
 
Walk Test mode is now active. 
3. 
 
Press Button 2 to exit Walk Test mode 
 
DELETE 