Communication Manager Maintenance-Object Repair Procedures
1914 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
 
System technician-demanded tests:
Descriptions and Error Codes
Investigate tests in the order presented below. Clearing Error Codes associated with the one 
test may also clear errors generated from other tests in the sequence.
Ring generator interchange test (#1539)
The ring generator interchange test causes a temporary interchange and is only used if the 
G650 has redundant power supplies. This test sends a command to the primary power supply in 
slot 0 to turn off ringing voltage, the ring arbitration lead changes state, and the secondary 
power supply in slot 15 provides ringing voltage to the backplane. The ring detection circuit for 
the secondary power supply is checked to verify that the secondary power supply is providing 
ringing voltage. 
A command is sent to the primary power supply to apply ringing and the ring arbitration lead 
changes back to allow the primary power supply to provide ringing voltage. The ring voltage 
detection circuit on the primary power supply is checked to verify that the primary supply is 
applying ring voltage. 
The long test sequence causes a ring interchange. However, the short test, which is the default, 
does not cause a ring interchange.
Order of investigation
Short test 
sequence
Long test 
sequence
D/ND
Ring Generator Interchange Test (#1539)
X
Nondestructive
Ring Generator Status Test (#1540)
X
X
Nondestructive
Table 702: Test #1539 Ring generator interchange 
Error
Code
Test
result
Description and recommendation
1000
ABRT
This is an internal system error.
1. Retry the command at 1-minute intervals up to 5 times.
1035
ABRT
The port network is not available.
1. Verify that the port network is not available by using the status 
port-network command
1990
ABRT
Both power supplies in the carrier are turned off.
 1 of 2