IGNITION CONTROL DIAGNOSTIC INDICATOR CHART
HEATING TIMING  CHART
0           15          22          45            52                                        0                                29             120, 135,150 
                 
 
 
 
      
 
 
 
      180*PG1348,60 ONLY
Circulator
Blower
On
Off
Seconds
Gas Valve
Igniter
Induced
Draft
Blower
Thermostat
On
Off
On
Off
On
Off
On
Off
Legend:           *PG10,12,24-60, *PG1324-42
                        *PG1348,60
100 %
50 %
COOLING TIMING  CHART
Seconds            0      7          30                                     0                   60
Circulator
Blower
Outdoor Fan
and
Compressor
Thermostat
ON
OFF
ON
OFF
ON
OFF
Legend:           *PG10,12,24-60, *PG1324-42
                        *PG1348,60
100 %
50 %
Light Signal
Refer to Abnormal Heating or Cooling Operation Sections of this Manual
Off
Internal Control Failure
1 Flash
External Lockout
2 Flashes
Pressure Switch Stuck Open
3 Flashes
Pressure Switch Stuck Closed
4 Flashes
Thermal Protection Device Open
5 Flashes
Flame Detected with Gas Valve Closed
6 Flashes
Short Cycle Compressor Delay (Cooling Only)