Gas-Fired Products 150 Manual De Usuario

Descargar
Página de 53
Form #43343530 
 
 
July 08 
–11– 
 
 
7.0) 
TYPICAL LAYOUTS – PTU / PTS Series 
 
Burner Box
Flue Termination
10 FT. Body Section
30 FT.
SYSTEM
40 FT.
SYSTEM
20 FT.
SYSTEM
50 FT.
SYSTEM
60 FT.
SYSTEM
70 FT.
SYSTEM
10FT.
SYSTEM
5 FT. Body Section
90 Deg. Elbow
180 Deg. U-Bend
LEGEND
 
EMITTER LENGTH 
BODY LENGTH 
MODEL 
Min. Max. 
MODEL 
Min. Max. 
PTS 40/25 
10 Ft. 
20 Ft. 
PTU 40/25 
10 Ft. 
10 Ft. 
PTS 50/30 
20 Ft 
30 Ft. 
PTU 50/30 
10 Ft. 
15 Ft. 
PTS 75/50 
20 Ft. 
30 Ft. 
PTU 75/50 
10 Ft. 
15 Ft 
PTS 100/65 
30 Ft. 
40 Ft. 
PTU 100/65 
15 Ft. 
20 Ft. 
PTS 125/80 
30 Ft 
50 Ft. 
PTU 125/80 
15 Ft. 
25 Ft. 
PTS 150/100 
40 Ft. 
60 Ft. 
PTU 150/100 
20 Ft. 
30 Ft. 
PTS 175/110 
50 Ft. 
70 Ft. 
PTU 175/110 
25 Ft. 
35 Ft. 
PTS 200/125 
50 Ft. 
70 Ft. 
PTU 200/125 
25 Ft. 
35 Ft. 
 
NOTES: 
1)  In all configurations, the control unit must be connected directly to either a) the 24-hole flange of the 10 ft. 
aluminized steel starting body section (for 10 ft., 20 ft., and 30 ft. systems) or b) the 6-hole flange of the 10 ft. 
alumi-therm steel starting body section (for 40 ft., 50 ft., 60 ft., and 70 ft. systems. 
2)  Joining of two 90º elbows directly together to form a “Z” shape IS NOT permitted. 
3)  PTS / U 175/110 - 40 ft length available for special applications. 
4)  5 Ft. Body Packages may be utilized on any of these heaters to yield heater lengths from 15 ft. to 70 ft. 
5)  Any configuration of components not shown in the illustrations may be used except as noted in 1 and 2