Problem
Cause
Corrective Action
Excessive Noise
Wheel Rubbing Inlet
Adjust wheel and/or inlet cone . Tighten wheel hub or bearing 
collars on shaft .
V-Belt Drive
Tighten sheaves on motor/fan shaft . Adjust belt tension . Align 
sheaves properly (see page 4) . Replace worn belts or sheaves .
Bearings
Replace defective bearing(s) . Lubricate bearings . Tighten 
collars & fasteners .
Wheel Unbalance
Clean all dirt off wheel . Check wheel balance, rebalance in 
place if necessary .
Low CFM
Fan
Check wheel for correct rotation . Increase fan speed .*
Duct System
See page 4 .
High CFM
Fan
Resize ductwork . Access door, filters, grills not installed .
Duct System
Change obstructions in system . Use correction factor to adjust 
for temperature/altitude . Resize ductwork . Clean filters/coils . 
Change fan speed .*
Static Pressure 
Wrong
Duct system has more 
or less restriction than 
anticipated
Check rotation of wheel . Adjust fan speed .
High Horsepower
Fan
Check rotation of wheel . Reduce fan speed .
Duct System
Resize ductwork . Check proper operation of face and bypass 
dampers . Check filters and access doors .
Fan Doesn’t Operate
Electrical Supply
Check fuses/circuit breakers . Check for switches off . Check for 
correct supply voltage .
Drive
Check for broken belts . Tighten loose pulleys .
Motor
Assure motor is correct horsepower and not tripping overload 
protector .
Overheated Bearing
Lubrication
Check for excessive or insufficient grease in the bearing .
Mechanical
Replace damaged bearing . Relieve excessive belt tension . 
Align bearings . Check for bent shaft .
NOTE: Always provide the unit model and serial numbers when requesting parts or service information .
* Always check motor amps and compare to nameplate rating . Excessive fan speed may overload the motor 
and result in burnout .
Troubleshooting
8
455308 • SWB / SFB / SFD, Rev. 6, June 2011 
Copyright 2011 © Greenheck Fan Corporation
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the 
shipment date . Any units or parts which prove to be defective during the warranty period will be replaced at our option 
when returned to our factory, transportation prepaid . Motors are warranted by the motor manufacturer for a period of one 
year . Should motors furnished by Greenheck prove defective during this period, they should be returned to the nearest 
authorized motor service station . Greenheck will not be responsible for any removal or installation costs .
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice.
Greenheck Centrifugal Utility Fan catalog provides additional 
information describing the equipment, fan performance, 
available accessories, and specification data .
®
Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: gfcinfo@greenheck.com • Website: www .greenheck .com
Warranty
AMCA Publication 410-96, Safety Practices for Users and 
Installers of Industrial and Commercial Fans, provides 
additional safety information . This publication can be 
obtained from AMCA International, Inc . at www .amca .org .