23
EcoBreeze System Installation
Remote display interface
See EcoBreeze remote display installation instructions for additional information.
The remote display interface enclosure contains the
 
LCD display that is used to control the 
EcoBreeze from a remote location. The EcoBreeze connects to the remote display interface 
over an expansion bus. 
N
OTE
: Separate incoming power cables from low voltage wiring by 150 mm (6 in.).
N
OTE
Communication wiring from the EcoBreeze to the remote display interface enclosure 
must be a minimum of 24-gauge, 3-core wire with shield with a maximum length of 300 m (984 
ft). 
1. Install the remote display interface enclosure in the desired location. 
I
MPORTANT
: For outdoor applications, use weather-proof conduit connectors. 
O
PERATING CONDITIONS
Ambient temperature 0 - 55°C (32 - 131°F). Relative 
humidity 5% - 95% non-condensing. 
N
OTE
Connect shield wire to GND.
2. Connect the bus wiring to the contacts labeled 124, 125, and 126 on the expansion bus 
terminal block, located behind the direct digital controller (DDC) access door on the 
Frame. 
NOTICE
DAMAGE TO EQUIPMENT
Damage to LCD display will result from exposure to temperatures below 0°C (32°F). 
Outdoor installations will require a third-party heat source as needed to ensure the LCD 
display is not subjected to temperatures below 0°C (32°F). 
Failure to follow these instructions can result in equipment damage.
na3716a
125
124
126
GND
DDC PANEL 
ENCLOSURE