Form 6104 BCF14N-R0299
Instruction Manual – Model CF1400 Oil Burner
Figure 12 – Air damper assembly
Table 5 –   Initial air adjusting plate settings
(damper position)
12
0
1
2
3
4
5
6 7
8 9 10 11
1409o-2
h
k
m
Legend (Figure 12)
Damper label - position indicator for air adjusting plate
Damper indicator - permanently attached to damper
Air adjusting plate - sets air position
Approximate 
head settings
Firing rate, gph
Tube “A”
Tube “B”
 0
4.00
4.00
 1
4.50
7.50
 2
5.00
8.00
 3
6.00
9.00
 4
7.00
10.00
 5
7.50
 6
8.00
7 – 10
NOTE 
These settings are approximate, and can
vary depending on actual job conditions
and overfire pressure.
  Set appliance limit controls
• Set the appliance limit controls in accordance with the
appliance manufacturer's recommendations.
  Prepare the fuel unit for air venting
• To vent air from one-pipe oil systems, attach a clear hose to
the vent plug on the fuel unit. Provide a container to catch
the oil. Loosen the vent plug.
• Vent the air as described under 
Start the burner
, page 14.