Model 700DD POOL
753  mm (29 5/8")
 
200 mm
(8")
FRONT VIEW
625 mm
(24 5/8 ")
730 mm
(28 3/4")
356 mm
(14")
210 mm
(8 1/4")
INLET SIDE
DRAIN CONNECTION
DIMENSIONS 700DDPOOL
 
 
mm (inches)
 
200 mm
(8")
730 mm
(28 3/4")
356 mm
(14")
159 mm
(6 1/4")
MOUNTING POINTS
 CONTROLS
DISCHARGE SIDE
EXHAUST AIR
TO OUTSIDE
EXHAUST AIR
FROM POOL
SUPPLY AIR
TO BUILDING
SUPPLY AIR
FROM OUTSIDE
NOTE: 
Service clearance
is 760 mm (30 in.)
from front 
access doors
 POOL AND 
DEFROST
AIR
165 mm
(6 1/2")
165 mm
(6 1/2")
All units conform to CSA and UL standards.
WARRANTY
All units carry a 15 year warranty on the heat recovery cores
and a 2 year replacement parts warranty.
AIRFLOWS (Each Air Stream)
423 (900)
378 (800)
329 (700)
282 (600)
235 (500)
190 (400)
143 (300)
  94 (200)
  42 (100)
AIRFLOW L/s (CFM)
25 (.1)   50 (.2)    75 (.3)  100 (.4)  125 (.5)  150 (.6)  175 (.7)
EXTERNAL STATIC PRESSURE IN PASCALS (IN. W.C.)
TOTAL CURRENT DRAW (AMPS) @ 120 VAC
5.5 HIGH
4.7 LOW
70%
60%
50%      
143
(300)
190
(400)
235
(500)
282
(600)
329
(700)
TEMPERATURE EFFECTIVENESS
AIRFLOW IN L/s (CFM)
NOTE: Exhaust Relative Humidity (RH) at 40%
EFFECTIVENESS
HIGH SPEED
HIGH SPEED
MED SPEED
MED SPEED
LOW SPEED
LOW SPEED
5.0 MED
PERFORMANCE
TI-104
1203
DATE: ____________________________________________PROJECT: _______________________________________
MECHANICAL CONTRACTOR: _________________________________________________________________________
SPECIFICATIONS
CORES
Modular (2 section) patented aluminum heat recovery cores arranged 
for efficient cross-flow ventilation.Meets the flame spread and smoke 
developed classifications of the National Building Code and NFPA 90A
(1993 Edition)
MOTORS 
Two PSC, 3 speed single shafted, 120 VAC, 2.75 Amps each (5.5 total on
high speed). HP - 1/10, 1625 RPM.  Watts - total on high speed - 648.
FILTERS 
Washable air filters in exhaust and supply air streams.
BLOWERS
Centrifugal type rated at 700 cfm (329 L/s) free air delivery. Each air
stream has one single shafted motor driving a centrifugal blower.
CONNECTION DUCT SIZES
Five - 14" x 8" H (356 mm x 200 mm H).
MOUNTING 
Unit to be set on support brackets hung by threaded rod type 
apparatus.  (brackets and rod not provided.)
CASE 
20 gauge prepainted galvanized steel (G60) for superior corrosion 
resistance. Insulated with foil faced insulation duct liner where required to
prevent exterior condensation. Drain connections; two - 1/2" (12 mm)
O.D.
CONTROLS
Illuminated power switch, 3 speed blower control, low voltage (24 VAC)
terminals for connection of remote dehumidistat (supplied) and defrost
light indicating automatic operation.
DEFROST 
Supply bypass routes indoor air to defrost core.
WEIGHT 142 lbs. (64.4 kg)   SHIPPING WEIGHT 167 lbs. (75.8 kg)