HBDV7 Series Direct Vent Gas Fireplace
6
54D8000
MIllIVolt CHeCK GAS PReSSuRe and eleCtRICAl INStAllAtIoN 
1.  Check gas type. The gas supply must be the same as 
stated on the appliance’s rating decal. If the gas supply 
is different from the fireplace, StoP! Do not install the 
appliance. Contact your dealer immediately.
.  To  ease  installation,  a  30"  (76  mm)  flex  line  with 
manual  shut-off  valve  has  been  provided  with  on 
this appliance. Install and attach 1/" gas line onto 
shut-off valve. 
3.  After completing gas line connection, purge air from 
gas line and test all gas joints from the gas meter 
to the fireplace for leaks. Use a solution of 50/40 
water and soap or a gas sniffer. 
4.  To adjust flame height, turn HI/LO knob to HI to get 
maximum pressure to burner. Turn HI/LO knob to 
LO to get minimum pressure. 
5.  To  check  gas  pressures  at  valve,  turn  captured 
screw counter clockwise  or 3 turns and then place 
tubing to pressure gauge over test point. Turn unit 
to high.  Figure 44. After taking pressure reading, 
be sure and turn captured screw clockwise firmly 
to reseal. Do not over torque. Check test points for 
gas leaks.
eleCtRICAl WIRING
This fireplace will work without any electrical supply. Electricity is only needed to operate blower.
NOTE: If installed in mobile home, fireplace must be bolted securely to floor. 
FP1979
Millivolt gas valve
FP1979
Figure 44 - 
Gas Pressure Check at Gas Valve
 
Pressure 
Test “IN”
Pressure 
Test “OUT”
HI/LO Knob
Pilot Adjustment Screw 
W
ARNING
Do  not  use  open  flame  to  check  for  gas 
leaks.
W
ARNING
electrical connections should only be performed 
by a qualified, licensed electrician. Main power 
must be off when connecting to main electrical 
power supply or performing service. All wiring 
shall be in compliance with all local, city and 
state codes. the appliance, when installed, must 
be  electrically  grounded  in  accordance  with 
local codes or in the absence of local codes, 
with the National electrical Code ANSI/NFPA 70 
(latest  edition)  and  Canadian  electrical  Code, 
CSA C22.1.
CA
ut
Io
N
label all wires before disconnecting when 
servicing controls. Wiring errors can cause 
improper and dangerous operation.
Verify proper operation after servicing.