CDVX Series Direct Vent Gas Fireplace
20012253
• 
Minimum clearances between vent pipe and com-
bustible materials are as follows:
  Top - 1” (25 mm)
  Sides - 1” (25 mm)
  Bottom - 1” (25 mm)
• 
The maximum horizontal distance between the end 
of the transition elbow in a corner application and the 
outside face of the rear wall is 20” (508 mm). (Fig. 16)
• 
Only one 45° elbow is allowed in these installations.
Top View
Straight Venting
Fig. 15  Rear vent applications.
20" 
(508 mm)
Max.
&0A
REAR
FP1598
20” (508 mm)
Max.
FP1188
Fig. 16  Rear vent application, one 45° elbow.
Rear Wall Installation
Twist Lock Pipe
STEP 1
Locate vent opening on the wall. To locate hole center 
consult with appropriate fireplace dimensions, Page 4. 
Frame as shown below.
Combustible Walls (Fig. 17)Cut a 9³⁄₈”H x 9³⁄₈” W 
(240 x 240 mm) hole through the exterior wall and 
frame as shown.  For 7TCRVT1320 cut a 10³⁄₈”H x 9³⁄₈” 
W (264 x 240 mm) hole.
Noncombustible Walls (Fig. 17): Hole opening must 
be 7¹⁄₂” (190 mm) in diameter. 
STEP 2
Install interior firestop as shown in Figure 18.
STEP 3
Remove telescoping collar from termination.
&0
FIRESTOP
Firestop
FP1600
Fig. 18  Install firestop.
Bend Tab
STEP 4
Bend tab on outer casing up and insert collar onto fire-
place collars. (Fig. 18)
STEP 5
Twist the termination collar so it locks onto fireplace col-
lars. Run screw through tab to keep collar from turning. 
(Fig. 19)
STEP 6
Slide fireplace into position.
STEP 7
From the outside of the house, slide the termination 
onto the collars.
STEP 8
Secure the termination to the house with the four (4) 
screws provided.
VO584-100
Vent Opening
2/99   djt
Vent Opening for Combustible Wall
9³⁄₈”
(240 mm)
9³⁄₈”
(240 mm)
Fireplace Hearth
Framing 
Detail
Opening for Noncom-
bustible Wall
7¹⁄₂”
(190 mm)
VO584-100
Fig. 17  Locate vent opening on wall.
When using all 
venting except 
7TCRVT1320
9³⁄₈”
(240 mm)
10³⁄₈”
(264 mm)
When using 
7TCRVT1320 
venting Only