Regency P33-NG4 Manual De Usuario

Descargar
Página de 52
Regency
®
 P33-4 Zero Clearance Direct Vent Gas Fireplace
9
INSTALLATION
3)  For exterior walls, insulate the enclosure to 
the same degree as the rest of the house, 
apply vapour barrier and drywall, as per 
local installation codes. (Do not insulate 
the fi replace itself.)
4)  The top of the unit must not be closer than 
30" (762mm) to the ceiling.
5)  Combustible material may be brought up to 
the top and sides of the unit and be covered 
with ceramic tiles, bricks, rock or other 
suitable combustible fi nishing materials.
Note:   The unit does not have to be completely 
enclosed in a chase. The clearance on 
top of the unit is 0" to the standoffs so 
combustible building materials can be 
laid directly on top of the standoffs. 
You must maintain clearance from 
the vent to combustible materials 
for fl ex or for Rigid Vent (Refer to 
"Clearances" Section).
1)  Determine the total thickness of facing 
material (e.g. drywall plus ceramic tiles) to 
allow the fi nished surface to be fl ush with 
the front of the unit. Total facing thickness 
can vary from 1/2" (13mm) to 1-1/4" (32mm) 
thick. 
6)  Use steel studs for framing where the 
1-1/2" (38mm) clearance from the vent 
to combustible material cannot be 
maintained.
2)  Frame in the enclosure for the unit with 
framing material. 
FRAMING AND FINISHING
16-1/2”
(419mm)
Minimum
4"
(102mm)
3"
(76mm)
1-1/2"
(38mm)
30”
(762mm)
10" (254mm)
dia. Hole through
wall for Dura-Vent
1/2"
(13mm)
Drywall
Top Header
Opening for gas
connection
12-3/4”
(324mm)
Minimum
4"
(102mm)
3"
(76mm)
1-1/2"
(38mm)
26”
(660mm)
10" (254mm)
dia. Hole through
wall for Flex
1/2"
(13mm)
Drywall
Top Header
Opening for gas
connection
Rigid Vent
Minimum Clearances
Flex Vent
Minimum Clearances
Vertical Termination or
Vertical Rise with Horizontal
Termination
NOTE: If this is an outside corner, the 
minimum distance between the vent and the 
outside corner is 6" (15cm) with AstroCap 
termination cap or 12" (30cm) with Rigid Vent 
termination cap. (For example Dura-Vent).
For Both Rigid & Flex
Rear Termination
NOTE: If this is an outside corner, the minimum 
distance between the vent and the outside 
corner is 6" (15cm) with AstroCap termination 
cap or 12" (30cm) with Rigid Vent termination 
cap. (For Example Dura-Vent).
For Rigid Vent
For Flex Vent
For Both Rigid & Flex
The  HeatWave Duct Kit has different 
clearance and framing requirements, 
check the HeatWave manual for details.
Install Side Nailing Strips, and Top Facing 
Support before unit is slipped into position.  
See "Unit Assembly Prior to Installation" 
Section