Regency P33-3 Zero Clearance Direct Vent Gas Fireplace
Wherever necessary due to 
external location of cap, the 
AstroCap can be replaced with 
the FPI Riser Vent Termination 
Cap or the Dura-Vent Snorkel 
Termination Cap.
6-7/8"
(173mm)
dia. Flue pipe
4" (102mm)
dia. flue pipe
Wall Thimble (2 pc)
(required in
Canada only)
Termination Cap
(Part# 946-523/P)
AstroCap
TM
spring
spacer
INSTALLATION
REGENCY DIRECT  VENT SYSTEM (FLEX)
HORIZONTAL TERMINATIONS ONLY
This venting system, in combination with the P33-3 Direct Vent Gas Fireplace, have been tested and listed as a direct vent heater system by Warnock 
Hersey. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram on page 10.
Regency Direct Vent (Flex) System Termination Kit (Part # 946-513) includes all the parts needed to install the P33-3 with a maximum 
run of 2 feet. If installing the P33 with a continuous vent length of more than 2 ft (.6m) to a maximum of 10 ft. (3.0m) using Kit # 946-515 (4 ft) or 
946-516 (10 ft) or see page 13 for alternate venting arrangements.
1)  6-7/8" dia. fl exible liner (2 ft. length)
2)  4" dia. fl exible liner (2 ft. length)
3)  spring spacers (3)
4) thimble 
(2)
5)  AstroCap termination cap (1)
6) screws 
(12)
7)  tube of Mill Pac (1)
8) plated 
screws 
(8)
9)  screws #8 x 1-1/2" drill point, stainless steel (4)
See also
Figure 1 below.
Notes: 
1)  Liner sections should be continuous without any 
joints or seams.
2)  Only Flex pipe purchased from Regency may be 
used for Flex installations.
Minimum
Simpson Dura-Vent Center-Line
Minimum Flex Kit Center-Line
Important
If using any Cabinet Mantels with Part 
# 510956, 510958, 510962, 510964 
and 510834 the wall thimble must 
be secured fi rst and venting must be 
attached to unit before sliding into 
fi nal position.
Also Simpson Dura-Vent venting can-
not be used with any of the mantels 
noted above.
Alternate Hori-
zontal Termi-
nation Caps
Figure 1