Regency P33-3 Zero Clearance Direct Vent Gas Fireplace
16-1/2”
(419mm)
Minimum
4"
(102mm)
3"
(76mm)
1-1/2"
(38mm)
30”
(762mm)
10" (254mm)
dia. Hole through
wall for Dura-Vent
1/2"
(13mm)
Drywall
Top Header
Opening for gas
connection
INSTALLATION
3)  For exterior walls, insulate the enclosure to 
the same degree as the rest of the house, 
apply vapour barrier and drywall, as per lo-
cal installation codes. (Do not insulate the 
fi replace itself.)
4)  The top of the unit must not be closer than 
30" (762mm) to the ceiling.
5)  Combustible material may be brought up to 
the top and sides of the unit and be covered 
with ceramic tiles, bricks, rock or other suit-
able combustible fi nishing materials.
Note:   The unit does not have to be complete-
ly enclosed in a chase. The clearance 
on top of the unit is 0" to the standoffs 
so combustible building materials can 
be laid directly on top of the standoffs. 
You must maintain clearance from the 
vent to combustible materials for fl ex 
for Simpson Dura-Vent, see page 7.
1)  Determine the total thickness of facing 
material (e.g. drywall plus ceramic tiles) to 
allow the fi nished surface to be fl ush with 
the front of the unit. Total facing thickness 
can vary from 1/2" (13mm) to 1-1/4" (32mm) 
thick. 
6)  Use steel studs for framing where the 
 
1-1/2" (38mm) clearance from the vent 
to combustible material cannot be main-
tained.
2)  Frame in the enclosure for the unit with 
framing material. 
Vertical Termination or
Vertical Rise with Horizontal
Termination
Rear Termination
FRAMING AND FINISHING
NOTE: If this is an outside corner, the 
minimum distance between the vent and the 
outside corner is 6" (15cm) with AstroCap 
termination cap or 12" (30cm) with Dura-Vent 
termination cap.
NOTE: If this is an outside corner, the minimum 
distance between the vent and the outside corner 
is 6" (15cm) with AstroCap termination cap or 12" 
(30cm) with Dura-Vent termination cap.
Simpson Dura-Vent Piping
Flex Piping
12-3/4”
(324mm)
Minimum
4"
(102mm)
3"
(76mm)
1-1/2"
(38mm)
26”
(660mm)
10" (254mm)
dia. Hole through
wall for Flex
1/2"
(13mm)
Drywall
Top Header
Opening for gas
connection
Simpson Dura-Vent
Minimum Clearances
Flex Pipe
Minimum Clearances
For Both Simpson & Flex
For Both Simpson & Flex
The HeatWave Duct Kit has different clear-
ance and framing requirements, check the 
HeatWave manual for details.
Install Side Nailing Strips, and Top Facing 
Support before unit is slipped into position.  
See page 9 for assembly details.