 P90 Zero Clearance Direct Vent Gas Fireplace
7
INSTALLATION
Side Wall Clearance 
6-1/2" (165mm)
Horizontal Vent Clearances
 Top 
2-1/2" 
(64mm)
 Side 
1-1/2" 
(38mm) 
 Bottom 
1-1/2" 
(38mm)
Vertical Vent Clearances 1-1/4" 
(32mm)
Alcove Clearances**:
 Max. 
Depth 36" 
(914mm)
 Min. 
Width 48" 
1219mm)
 Min. 
Height 72" 
1829mm)
* see mantle clearance instructions 
(Refer to the "Combustible Mantels" section).
CLEARANCES
The clearances listed below are Minimum 
distances unless otherwise stated:
A major cause of chimney related fi res is 
failure to maintain required clearances (air 
space) to combustible materials. It is of the 
greatest importance that this fi replace and 
vent system be installed only in accordance 
with these instructions.
LOCATING YOUR 
GAS FIREPLACE
1)  When selecting a location for your fi replace, 
ensure that the clearances outlined on this 
page are met.
2)  P r o v i d e   a d e q u a t e   c l e a r a n c e s  f o r 
servicing.
3)  The appliance must be installed on a fl at, 
solid, continuous surface (e.g. wood, metal, 
concrete). This may be the fl oor, or raised up 
on a platform to enhance its visual impact. 
If the appliance is going to be installed 
on carpeting, combustible linoleum tile or 
other combustible material other than wood 
fl ooring, the appliance must be installed on 
a metal or wood panel extending the full 
width and depth of the appliance.
4)  The P90 Direct Vent Gas Fireplace can 
be installed in a recessed position or 
framed out into the room as in A, B, C, D. 
 
See Diagram 1.
MANUFACTURED 
MOBILE HOME 
ADDITIONAL 
REQUIREMENTS
1)  Ensure that structural members are not cut 
or weakened during installation.
2) Ensure proper grounding using the #8 ground 
lug provided. See the "Wiring Diagram" 
section.
5)  This appliance is Listed for bedroom 
 
installations when used with a Listed Millivolt 
Thermostat. Some areas may have further 
requirements, check local codes before 
installation.
6)  The P90 Direct Vent Gas Fireplace is 
approved for alcove installations, which 
meet the clearances listed on this page.
7)  We recommend that you plan your instal-
lation on paper using exact measurements 
for clearances and fl oor protection before 
actually installing this appliance. Have a 
qualifi ed inspector, dealer, or installer review 
your plans before installation.
Note:   For vent terminations see the 
"Exterior Vent Termination
  
Locations" 
section.
Diagram 1
A) Flat 
on 
Wall
B) Flat 
on 
Wall 
Corner
C) Recessed 
into 
 Wall/Alcove
D) Corner 
 
HEATWAVE 
DUCT SYSTEM 
OPTIONAL KIT 
#946-556
The  HeatWave Air Duct Kit increases the 
effectiveness of your fi replace by dispersing 
warm air from the fi replace to remote locations in 
the same room or other rooms in your home.
Up to  two kits may be installed on the fi replace. 
Please Note: Only 1 HeatWave kit may be 
operated at one time. This includes the internal  
blower option as well. 
OPTIONAL 
HEAT RELEASE KIT
#946-570
The Heat  Release Kit expels warm air from 
the fi replace to the outside of the building, 
allowing the fi replace to be operated with less 
heat entering the room. The kit may be used 
on either the left or right side.
WARNING: 
Fire hazard is an extreme risk 
if these clearances are not 
adhered to.
Clearances for HeatWave and 
Heat Release Kit
Heat Release Kit
The HeatWave Duct Kit and the Heat Release 
Kit have different clearance and framing 
requirements, check the HeatWave and Heat 
Release manual for details.
Clearance to Combustibles from:
  Back
 0" 
(0mm) 
  Side 0" 
(0mm)
  Floor 0" 
(0mm) 
 
NOTE: The minimum fl oor clearance must 
be maintained from the top surface of the 
carpeting, tile, etc.