wall  thimble  will  conceal  it  (see  left  image  in 
Figure 26).
7.  Slide the decorative wall thimble up to the wall 
surface  and  attach  with  the  screws  provided. 
Apply decorative brass or chrome trim if desired 
(see right image in Figure 26). 
NOTES:  
•  The four wood screws provided should be replaced 
with  the  appropriate  fasteners  for  stucco,  brick, 
concrete, or other types of siding.
•  For  buildings  with  vinyl  siding,  a  vinyl  siding 
standoff, should be installed between the vent cap 
and the exterior wall (see Figure 27). Attach the 
vinyl siding standoff to the horizontal termination. 
The vinyl siding standoff prevents excessive heat 
from  possibly  melting  the  vinyl  siding  material. 
Note  that  the  horizontal  vent  termination  bolts 
onto  the  flat  portion  of  the  vinyl  siding  standoff 
(shaded area in Figure 27), so that an air space will 
exist between the wall and the vent termination.
•  The horizontal run of vent pipe must be level and 
should have a 1⁄4 inch rise for every one foot 
of run towards the termination. Never allow 
the vent to run downward. This could cause high 
temperature and may present the possibility of a 
fire.
•  The  location  of  the  horizontal  vent  termination 
on  the  exterior  wall  must  not  be  easily  blocked 
or obstructed. Refer to “Initial Installation - Vent 
Termination Restrictions” section.
  When installing a vent pipe in a chase the minimum 
clearance to combustibles is 2” (5 cm).
Figure 27: Installing Vent Cap with Vinyl Siding 
Stand-Off.
Figure 28: Installing Horizontal Vent Termination.
4.  Position the horizontal vent termination in the center of the 10” (25.4 cm) x 10” (25.4 cm) hole, and 
attach to the exterior wall with the four screws provided. Before attaching the vent termination to the 
exterior wall, run a bead of non-hardening mastic around the edges, so as to make a seal between 
the termination and the wall. The arrow on the vent termination should be pointing up, insure that 
the proper clearances to combustible materials are maintained.
5.  Before  connecting  the  horizontal  run  of  the  vent  pipe  to  the  vent  termination,  slide  the  black 
decorative wall thimble cover over the vent pipe.
6.  Slide the appliance and vent assembly towards the wall, carefully inserting the vent pipe into the 
cap assembly. It is important that the vent pipe extend into the vent cap a sufficient distance with a 
minimum of 11⁄4” (3.2 cm) overlap. Secure the connection between the vent cap pipe and the vent 
cap by attaching the two sheet metal straps extending from the vent cap assembly into the outer wall 
of the vent pipe. Use the two sheet metal screws provided to connect the straps to the vent pipe. 
Bend any remaining portion of the sheet metal straps back towards the vent cap, so the decorative 
21
Initial Installation
QUALIFIED INSTALLERS ONLY