Dutchwest Non-Catalytic Convection Heater
30002278
1. Shielding for a top exit stove must include a flue collar shield to protect the area behind the flue collar.
2. Chimney connector heat shields must extend exactly 24” (610 mm) above the flue collar of the stove.
3. Dimension is to the top plate of the stove, not the back wall of the stove.
2. Chimney connector heat shields must extend exactly 24” (610 mm) above the flue collar of the stove.
3. Dimension is to the top plate of the stove, not the back wall of the stove.
Stove and Chimney Connector Clearance Charts
Stove Clearance
Side
Rear
3
Corner
Side
Rear
3
Corner
No heat shields
(A) 20”
(B) 25”
(C) 15¹⁄₂”
(D) 7”
(E) 19”
(F) 10¹⁄₂”
(508 mm)
(635 mm)
(394 mm)
(178 mm)
(483 mm)
(267 mm)
Rear exit,
(G) 16”
(H) 12”
N/A
N/A
N/A
N/A
flue collar heat shields
(406 mm)
(305 mm)
Top exit
1,2
, flue collar
(K) 14”
(L) 15”
(M) 7¹⁄₂”
(N) 7”
(O) 11”
(P) 7”
Single-wall connector
(356 mm)
(381 mm)
(191 mm)
(178 mm)
(279 mm)
(178 mm)
w/connector heat shield
Right Side
Right Side
and right side heat shield
Only
Only
Top exit
1
, flue collar
(K) 17”
(L) 15”
(M) 7¹⁄₂”
(N) 8”
(O) 14¹⁄₂”
(P) 7”
heat shield,
(432 mm)
(381 mm)
(191 mm)
(178 mm)
(368 mm)
(178 mm)
Double wall connector
Chimney Connector Clearance:
Single-wall connector
Chimney Connector Clearance:
Single-wall connector
20”
14”
No connector heat shield
(508 mm)
(356 mm)
Single-wall
2
connector
10”
6”
w/connector heat shield
(254 mm)
(152 mm)
& flue collar heat shield
Double-wall connector
Double-wall connector
10”
9¹⁄₂”
& flue collar heat shield
(254 mm)
(241 mm)
Front Clearance to Combustibles:
(All Installations)
48” (1219 mm)
Model 2478 Medium Convection Heater
UNPROTECTED SURFACES
PROTECTED SURFACES
Corner
Corner
Parallel Installations
Installations Parallel Installations
Installations
Important:
When choosing an installation utilizing the side loading door located on the left side of the stove, follow the
minimum dimensions given in the Stove and Chimney Connector Chart on Page 13 and the Minimum Dimen-
sions for Noncombustible Floor Protectors given on Page 9, Figure 12.
For operation of the side loading door, the minimum clearances on the left side of the stove for usable opera-
tion is 13” (330 mm) in a corner installation and 18” (457 mm) in a parallel installation.
When choosing an installation utilizing the side loading door located on the left side of the stove, follow the
minimum dimensions given in the Stove and Chimney Connector Chart on Page 13 and the Minimum Dimen-
sions for Noncombustible Floor Protectors given on Page 9, Figure 12.
For operation of the side loading door, the minimum clearances on the left side of the stove for usable opera-
tion is 13” (330 mm) in a corner installation and 18” (457 mm) in a parallel installation.