GAS SUPPLY
Check all local codes for requirements, especially for the size and type 
of gas supply line required.
Note: Never use plastic pipe. Check to confirm whether your local codes 
allow copper tubing or galvanized.
Note: Since some municipalities have additional local codes, it is always 
best to consult your local authority and installation code.
Recommended Gas Pipe Diameter
  Pipe Length 
Schedule 40 Pipe 
Tubing, Type L
 
(Feet) 
Inside Diameter 
Outside Diameter
 
 
Nat. 
L.P. 
Nat. 
L.P.
 
0-10 
1/2" 
3/8" 
1/2" 
3/8"
 
 
12.7mm  9.5mm 
12.7mm     9.5mm
 
10-40 
1/2" 
1/2" 
5/8" 
1/2"
 
 
12.7mm  12.7mm  
15.9mm   12.7mm
  40-100 
1/2" 
1/2" 
3/4" 
1/2"
 
 
12.7mm  12.7mm 
19mm      12.7mm
  100-150 
3/4" 
1/2" 
7/8" 
3/4"
 
 
19mm 
12.7mm 
22.2mm  19mm
Figure 1
Installing a New Main Gas Cock 
Each appliance should have its own manual gas cock.
A  manual  main  gas  cock  should  be  located  in  the  vicinity  of 
the unit. Where none exists, or where its size or location is not 
adequate, contact your local authorized installer for installation 
or relocation.
Compounds used on threaded joints of gas piping shall be resistant 
to the action of liquefied petroleum gases. The gas lines must be 
checked for leaks by the installer. This should be done with a soap 
solution watching for bubbles on all exposed connections, and if 
unexposed, a pressure test should be made. 
Never use an exposed flame to check for leaks. Appliance must be 
disconnected from piping at inlet of control valve and pipe capped 
or plugged for pressure test. Never pressure test with appliance 
connected; control valve will sustain damage!
A gas valve and ground joint union should be installed in the gas 
line upstream of the gas control to aid in servicing. It is required 
by the National Fuel Gas Code that a drip line be installed near 
the gas inlet. This should consist of a vertical length of pipe tee 
connected into the gas line that is capped on the bottom in which 
condensation and foreign particles may collect.
Method of Installing a Tee Fitting Sediment Trap
The use of the following gas connectors is recommended:
— ANS Z21.24 Appliance Connectors of Corrugated Metal Tubing 
and Fittings
— ANS Z21.45 Assembled Flexible Appliance Connectors of Other 
Than All-Metal Construction
The above connectors may be used if acceptable by the authority 
having jurisdiction. The state of Massachusetts requires that a flexible 
appliance connector cannot exceed three feet in length.
Pressure Testing of the Gas Supply System
1.  To check the inlet pressure to the gas valve, a 1/8" (3mm) N.P.T. 
plugged tapping, accessible for test gauge connection, must be 
placed immediately upstream of the gas supply connection to 
the appliance.
2. The  appliance  and  its  appliance  main    gas    valve  must  be 
disconnected  from  the  gas  supply  piping  system  during  any 
pressure testing of that system at test pressures in excess of 1/2 
psig (3.5 kPa).
3.  The appliance must be isolated from the gas supply piping system 
by closing its equipment shutoff valve during any pressure testing 
of the gas supply piping system at test pressures equal to or less 
than 1/2 psig (3.5 kPa).
Attention! If one of the above procedures results in pressures in 
excess of 1/2 psig (14" w.c.) (3.5 kPa) on the appliance gas valve, 
it will result in a hazardous condition.
Checking Manifold Pressure
VFCR-25 Natural gas will have a manifold pressure of approximately 
3.5"  w.c.  (.871kPa)  for  maximum  input  or  1.7"  w.c.  (.423kPa) 
for minimum input at the pressure regulator outlet with the inlet 
pressure to the pressure regulator from a minimum of 4.5" w.c. 
(1.120kPa) for the purpose of input adjustment to a maximum of 
10.5" w.c. (2.614kPa). VFCM-25 and VFCT-25 Natural gas will 
have a manifold pressure of approximately 6.0" w.c. (1.49kPa) at 
the pressure regulator outlet with the inlet pressure to the pressure 
regulator from a minimum of 7.0" w.c. (1.74kPa) for the purpose of 
input adjustment to a maximum of 10.5" w.c. (2.615kPa). VFCR-25 
Propane gas will have a manifold pressure approximately 10.0"w.c. 
(2.49kPa) for maximum input or 6.3"w.c. (1.568kPa) for minimum 
input at the pressure regulator outlet with the inlet pressure to the 
pressure regulator from a minimum of 11.0"w.c. (2.739kPa) for the 
purpose of input adjustment to a maximum of 13.0"w.c. (3.237kPa). 
VFCM-25 and VFCT-25 Propane gas will have a manifold pressure 
approximately 10.0"w.c. (2.49kPa) at the pressure regulator outlet 
with the inlet pressure to the pressure regulator from a minimum 
of 11.0"w.c. (2.739kPa) for the purpose of input adjustment to a 
maximum of 13.0"w.c. (3.237kPa). 
NOTE: The gas control is equipped with a captured screw type 
pressure test point, therefore it is not necessary to provide a 1/8" 
test point up stream of the control.
A test gauge connection is located downstream of the gas appliance 
pressure regulator for measuring gas pressure. The connection is a 
1/8 inch 3mm) N.P.T. plugged tapping.