Hampton Direct H35-NG1 Manual De Usuario

Descargar
Página de 48
26
Hampton
®
 H35 Direct Vent Freestanding Gas Stove
GAS PIPE 
PRESSURE TESTING
The appliance must be isolated from the gas 
supply piping system by closing its individual 
manual shut-off valve during any pressure 
testing of the gas supply piping system at test 
pressures equal to or less than 1/2 psig. (3.45 
kPa).  Disconnect piping from valve at pressures 
over 1/2 psig.
The manifold pressure is controlled by a regulator 
built into the gas control, and should be checked 
at the pressure test point.
Note:    To properly check gas pressure, both 
inlet and manifold pressures should 
be checked using the valve pressure 
ports on the valve.
1)  Make sure the valve is in the "OFF" posi-
tion.
2)  Loosen the "IN" and/or "OUT" pressure 
tap(s), turning counterclockwise with a 1/8" 
wide fl at screwdriver.
3)  Attach manometer to "IN" and/or "OUT" 
pressure tap(s) using a 5/16" ID hose.
4)  Light the pilot and turn the valve to "ON" 
position. Read manometer.
To adjust the aeration: use the allen key to turn 
the turning gear which will adjust the air shutter. 
Open the air shutter for a blue fl ame or close it 
for a yellower fl ame. 
Caution: Carbon will be produced if the air 
shutter is closed too much.
Note:  Any damage due to carboning re-
sulting from improperly setting the 
aeration controls is NOT covered 
under warranty.
Note:  Aeration Adjustment should only be 
performed by an authorized Hamp-
ton
®
 Installer at the time of installation 
or service.
5)  The pressure check should be carried out 
with the unit burning and the setting should 
be within the limits specifi ed on the safety 
label.
6) When fi 
nished reading manometer, turn 
off the gas valve, disconnect the hose and 
tighten the screw (clockwise) with a 1/8" fl at 
screwdriver. Note: Screw should be snug, 
but not overtightened.
 
Valve Description
1) Gas 
on/off 
knob
2) Manual 
high/low 
adjustment
3) Pilot 
Adjustment
4) Thermocouple 
Connection
5) Main 
Operator
6)  Outlet Pressure Tap (Manifold Pressure)
7)  Inlet Pressure Tap (Supply Pressure)
8) Pilot 
Outlet
9) Main 
Gas 
Outlet
10) Flange Securing Screw Holes
11) Alternative TC Connection Point
12) Thermoelectric Unit
13) Additional Valve Mounting Hole
INSTALLATION
AERATION 
ADJUSTMENT
The burner aeration is factory set but may need 
adjusting due to either the local gas supply, air 
supply or altitude. 
Natural Gas  
1/4" (6.4 mm) 
Propane 3/8" 
(9.5 
mm) 
The aeration adjustment gears are located on 
the right side of the burner box.  Remove the 
Hampton
®
 Logo plate on the right side of the 
unit to access the adjustment gears.
Clockwise to open, 
counter-clockwise to close.