HEATING CYCLE ANALYSIS
COOLING CYCLE ANALYSIS
HEAT OF EXTRACTION (ABSORPTION) OR HEAT OF REJECTION =
FLOW RATE (GPM) x
TEMP. DIFF. (DEG. F) x
FLUID FACTOR* =
(Btu/hr)
SUPERHEAT = SUCTION TEMPERATURE – SUCTION SATURATION TEMPERATURE
=
 
(DEG F)
SUBCOOLING = DISCHARGE SATURATION TEMPERATURE – LIQUID LINE TEMPERATURE
=
 
(DEG F)
*Use 500 for water, 485 for antifreeze.
SUCTION
COMPRESSOR
DISCHARGE
COAX
EXPANSION
VALVE
F
F
AIR
COIL
F
PSI
WATER OUT
WATER IN
F
PSI
LOOK UP PRESSURE DROP IN TABLE 23
TO DETERMINE FLOW RATE
F
LIQUID LINE
PSI
F
SAT
a50-8445
SUCTION 
COMPRESSOR 
DISCHARGE 
COAX 
EXP ANSION 
VA LV E 
°F 
°F 
AI R 
COI L 
°F 
PSI 
WA TER OUT 
WA TER IN 
°F 
PSI 
LOOK UP  PRESSURE DROP  IN  T ABLE 23
TO  DETERMINE FLOW RA TE 
°F 
LIQUID LIN E 
PSI 
°F 
SA T 
a50-8446
97B0038N05