UK Conditions: Cooling Indoor 23˚C DB 50% RH Outdoor 30˚C  Heating Indoor 20˚C Outdoor 0˚C
Rating Conditions: Cooling Indoor 27˚C DB 19˚C WB Outdoor 35˚C DB 24˚C WB  Heating Indoor 20˚C DB Outdoor 7˚C DB 6˚C WB
2
UK Conditions: Cooling Indoor 23˚C DB 50% RH Outdoor 30˚C  Heating Indoor 20˚C Outdoor 0˚C
Rating Conditions: Cooling Indoor 27˚C DB 19˚C WB Outdoor 35˚C DB 24˚C WB  Heating Indoor 20˚C DB Outdoor 7˚C DB 6˚C WB
ECOi - 2 and 3 pipe electric VRF systems
Benefits
Ease of installation
R410A  has  a  higher  operating  pressure  with  a  lower  pressure 
loss than previous refrigerants. This enables smaller pipe sizes to 
be used and allows reduced refrigerant charges.
L3
L4
H2
H1
L2
Ln
L1
Category
Item
Description
Max length (m)
Allowable pipework length
L1
Maximum pipe run in one direction
Actual length
150
Equivalent length
175
L2-L3
Difference between maximum length and minimum length from the  
first distribution joint
40
L3 L4 Ln
Maximum length of each distribution joint
30
L1+L3+L4
Maximum total pipe run length
300
Allowable
height
difference
H1
When outdoor unit installed higher
50
When outdoor unit installed lower
40
H2
Maximum difference between indoor units
15
Easy to control
A  wide  variety  of  control  options  are  available  to  ensure 
that  the  ECOi  system  provides  the  user  with  the  degree 
of  control  that  they  desire,  from  simple  room  controllers 
through to state of the art BMS controls. 
Simple to commission
Simple  set-up  procedure  including  automatic  addressing  of 
connected  indoor  units.  Configuration  settings  can  be  made 
from an outdoor unit or via a remote controller.
Accurate capacity control
To  ensure  that  the  compressor  capacity  is  matched  to 
building  load  as  accurately  and  efficiently  as  possible, 
SANYO  has  designed  its  range  of  2  and  3  way  ECOi 
systems  to  operate  with  DC  inverter  and  high-efficiency 
fixed  speed  compressors.  The  system  selects  the  most 
efficient  compressor  to  operate  by  dynamically  monitoring 
the  building  load  and  choosing  the  best  compressor 
combination to run.
Easy to maintain
Each  system  allows  the  use  of  prognostic  and  diagnostic 
controls  routines,  from  refrigerant  charge  control  through  to 
complex  fault  code  diagnostics,  all  designed  to  reduce  the 
speed of maintenance calls and unit down time.
Lower running and life cycle costs 
SANYO  ECOi  VRF  systems  are  amongst  the  most  efficient 
VRF  systems  on  the  market,  offering  COPs  in  excess  of  4.0 
at  full  load  conditions.  The  system  is  also  designed  to  make 
sure  that  we  reduce  the  running  cost  of  each  system  by 
using  our  unique  road  map  control  routine  to  ensure  that 
the  most  efficient  combination  of  compressors  are  running 
at  any  one  time.  Improved  defrost  sequencing  also  reduces 
running  cost  by  defrosting  each  outdoor  coil  in  turn  when 
conditions allow.
Since its formation in 1958, SANYO Air Conditioners 
has  been  at  the  forefront  of  innovation  with  its 
market-leading research and development program. 
From  the  world’s  first  heat  pump  air  conditioner  in 
1960 to the first 3 pipe VRF system in 1989, SANYO 
continues  to  deliver  leading  technology  combined 
with  the  reliability  and  customer  service  that  you 
would  expect  from  a  global  brand  like  SANYO.
0
5
10
15
20
25
30
35
40
8HP 10HP
ECOi system capacity
12HP 14HP 16HP 18HP 20HP 22HP 24HP - 48HP
13
16
19
23
26
29
33
36
40
Number of indoor units
Simple to design
SANYO  recognise  that  designing,  selecting  and  preparing  a 
professional VRF quotation can be a time consuming and costly 
process, especially as it is often also a speculative exercise. So 
we have designed proprietary software which is quick and easy 
to  use  and  produces  a  full  schematic  layout  of  pipework  and 
controls, as well as a full materials list and performance data.
Easy to position
The compact design of the ECOi outdoor units means that they 
fit into a standard lift and are easy to handle and position when 
on site. The small footprint and modular appearance of the units 
ensure a cohesive appearance to an installation.
Off-coil temperature control 
SANYO ducted units offer the unique advantage of being able to 
offer off-coil temperature coil as standard. This allows designers 
to select units using an off coil temperature between 7°C and 
22°C.  This  allows  room  environments  to  be  cooled  without 
subjecting  its  occupants  to  cold  drafts  or  uncomfortable 
conditions. This is achieved without any extra controls or wiring 
to each unit.
Wide selection and connectability
With 15 indoor model styles available, ECOi systems are the ideal 
choice for multiple small capacity indoor unit installations, with 
the ability to connect up to 40 indoor units to systems of 24HP 
or greater.
Flexible pipe length