9-4-2. Poor cooling or heating.
9-4-3. Excessive cooling or heating.
NO
NO
• Set temperature is suitable.
Set temperature to higher or 
lower value using temperature 
setting buttons of the remote 
control unit.
• Remote control unit is placed where 
it can detect room temperature 
properly.
Change position of remote 
control unit.
Air filter is clogged.
NO
YES
Temperature
difference
is small.
YES
Temperature difference between
suction and discharge air is
large enough (approx. 10 deg. or more).
Possibility of
gas shortage.
YES
• Check position of remote control unit. 
Cool or warm air from air conditioner 
reaches position directly.
Change position of remote 
control unit.
• Wide and narrow tubes between 
indoor unit and outdoor unit are 
insulated.
Insulate both wide and narrow 
tubes separately and then 
tape together.
• Measure temperature of suction and 
discharge air of air conditioner.
Charge refrigerant 
gas (R22).
Check for clogging of air filter.
• Fan speed is set to LOW.
Clean filter.
Set fan speed to either 
HIGH or MEDIUM.
• Review cooling load estimate, 
if performance of air conditioner is 
normal.
Reduce cooling or heating 
load or replace the air 
conditioner with larger 
capacity.