Startup Procedures 
Siemens Building Technologies, Inc. 
 
35 
 
Parameter Description 
Action 
Setting/ 
Default 
P1211 
Number of Restart Attempts
 
Specifies the number of times 
SED2 will attempt to restart after 
supply power brownout or fault, if 
P1210 automatic restart is 
activated.  
1. Press   to enter the SED2 
parameter mode and to display 
r0000
.  
2. Press   to advance to 
parameter P1211.  
3. Press   to access the 
parameter values level. 
4. Press   to advance to 
desired value.  
5. Press   to confirm and save 
the setting. 
Minimum = 0 
Default = 3 
Maximum = 10 
Suggested = 
10 
P1212 
Time to First Restart 
Selects the time (seconds) 
before the SED2 is restarted for 
the first time if P1210 automatic 
restart is activated.  
1. Press   to enter the SED2 
parameter mode and to display 
r0000
.  
2. Press   to advance to 
parameter P1212.  
3. Press   to access the 
parameter values level. 
4. Press   to advance to 
desired value.  
5. Press   to confirm and save 
the setting. 
Minimum = 0 
Default = 3 
Maximum = 10 
Suggested = 
10