Friedrich RC 12 Manual De Usuario

Descargar
Página de 26
18
www.retroaire.com
The Right Fit For Comfort
IMPORTANT: The RC/RH90 chassis is 18 1/4” deep for 
the 9,000, 12,000, and 15,000 Btuh models. The standard 
depth for the 18,000 Btuh is 24”. However, EMI can supply 
it for an 18 1/4” chassis on demand.
RC/RH90 REPLACEMENT PTAC
INSTALLATION INSTRUCTIONS
1. Remove unit from box and install duct collar.
• 1 Installation Manual
• 1 Lt. & Rt. Baffl es
• 1 Duct Collar
• 1 Slide-Duct
• Screws 
• 1/4” x 3/4” Open Cell Foam Tape
• 1” x 1” Open Cell Foam Tape
• 1/2” x 1/2” Open Cell Foam Tape
HYDRONIC
 ONLY
• 1ea. 2-Position Connector & Pin Mate
• 14AWG Yellow Wire
RC/RH90 BAFFLE INSTALLATION KIT
2. Slide unit into wall sleeve. The supply duct on the cool-
ing chassis should line up with the supply vent on the 
room cabinet. The weather angles should require no 
adjustment. 
IMPORTANT: The correct condenser air baffl es must 
be installed or performances may be impaired and/or 
the warranty will be voided. 
Figure A9
NOTE:  CONTROL  BOX  IS 
A  SEPARATE  PART  THAT 
IS  ELECTRICALLY  CON-
NECTED TO THE CHASSIS 
ON-SITE.
Install Duct Collar here
3. Baffl e Installation - Remove baffl es from kit bag sup-
plied with unit. Install left and right side baffl es on the 
condenser coil in existing holes: 
• Baffl es must come in contact with the outdoor louver  
•  Make  sure  baffl es  are  directed  inward  toward  the 
center of coil 
• Secure baffl es tightly to the condenser coil using the 
screws provided (Figure A9)
4. Remove 1/2” x 1/2” open cell foam strips from kit bag 
and apply to sheet metal fl anges around the perimeter 
of the supply air duct outlet as shown in Figure A9. Fail-
ure to do so results in recirculation of the conditioned air 
around the wall sleeve and through the unit causing the 
unit to short cycle, thus raising operating costs through 
improper heating and cooling.
Figure B9
Duct Collar and Slide-Duct Installation 
• Remove duct collar and slide-duct from packaging.
• Fasten 1/4” x 1/2” foam tape to the bottom fl anges 
of the duct collar, this serves as a gasket between 
the collar and the unit. 
• Securely fasten  duct collar over discharge opening 
with screws provided.
•  Insert  slide-duct  into  duct  collar.  (See  illustration 
above)
5. 1” x 1” Open cell foam strips  are provided to prevent 
outside  air  from  entering  around  the  chassis  to  the 
room from the sides and top of the cabinet (Figure B9)
Install between wall sleeve and cooling chassis. It is 
imperative to have a solid air seal between wall sleeve 
and chassis. Failure to do so will result in air leakage 
from outdoor to indoor causing system problems i.e. 
coils freezing, short cycling, and constant running of 
unit. If installer is in need of more foam than supplied 
in kit, consult factory.
1/2” X 1/2” 
Supply Air 
Duct Foam Tape
Baffl es-Directed Inward 
Toward Coil
��������
�������
���
���������������
��������������
Front View
Cooling Chassis
Wall Sleeve
1�x1� Foam Tape