Ductless_Ceiling_Floor_Heat_Pumps_Submittal_11
Ductless Split Systems
Ceiling and floor installed heat pumps
Refrigeration line sets
Insulated line sets are available for all Friedrich split systems in 
15 ft. and 35 ft. lengths. Each line set is equipped with flare nuts 
on both ends. Both liquid and suction lines are insulated. Line 
sets can be joined together with field supplied double female 
connectors. Each system requires one line set for each indoor 
unit installed. On multi-zone systems, line sets should be ordered 
based on individual indoor unit capacities not total system 
capacity.  For example, a M18DYF uses 2 line sets for 9,000 Btu 
units, not 1 for the 18,000 Btu product.
NOTE: All models have low ambient 
capabilities built-in. Capacity is 
reduced as 0 degrees Fahrenheit is 
approached.
NOTE: All R410A models have 1/2˝ 
UNF 20 thread per inch charging and 
vacuuming ports. An adapter must be 
used for 1/4˝ gauges. Adapter part 
number 67270018 is available through 
Friedrich parts distributors.
Due to continuing research in 
new energy-saving technology, 
specifications are subject to change 
without notice.
Specifications
PERFORMANCE RATINGS
SYSTEM MODEL NO.
S24YF
S36YF
C24YF
INDOOR MODEL
MS24Y3F
MS36Y3F
MC24Y3F
OUTDOOR MODEL
MR24UY3F
MR36Y3F
MR24UY3F
CAPACITY COOLING
Btu
22200
34100
22200
CAPACITY COOLING MIN - MAx
Btu
5000-27300
8500-36000
5000-27300
SENSIBLE HEAT RATIO
0.62
0.67
0.64
CAPACITY HEATING @ 47°F
Btu
24,200
38,200
24,200
CAPACITY HEATING MIN - MAx
Btu
5000-29000
9200-42700
5000-29000
CAPACITY HEATING @ 17°F
Btu
20,100
27,100
20,100
HSPF
8.5
8.5
8.5
SEER
15
14
15
EER
9.8
8.1
10.6
MOISTURE REMOvAL
Pts/h
7.4
7.4
6.4
AIRFLOw (LOw, MED, HIGH)
CFM
371, 436, 518
842, 977, 1089
436, 536, 618
SOUND RATING - INDOOR
dB-A
38, 43, 47
41, 45, 48
38, 43, 45
SOUND RATING - OUTDOOR
dB-A
53
54
53
OPERATIONG RANGE (HEATING)
°F
0 - 115 (14 - 75)
0 - 115 (14 - 75)
0 - 115 (14 - 75)
EST. YEARLY OPERATING COST 
$180
$337
$168
ELECTRICAL DATA
POwER SOURCE
230/208-60-1
230/208-60-1
230/208-60-1
MIN. AMPACITY
A
15.5
23
15.5
COOLING wATTS
w
2250
4220
2100
MAx. TD FUSE/BREAkER
A
20
30
20
REFRIGERATION SYSTEM
REFRIGERANT
R410A
R410A
R410A
COMPRESSOR TYPE
Inverter (Twin Rotary)
Inverter (Twin Rotary)
Inverter (Twin Rotary)
CONNECTIONS
Flare
Flare
Flare
LIqUID LINE O.D.
in
3/8"
3/8"
3/8"
SUCTION LINE O.D.
in
5/8"
5/8"
5/8"
FACTORY PRECHARGE
ft
50'
50'
50'
MAx. LINE LENGTH
ft
165'
165'
165'
MAx. HEIGHT DIFFERENCE
ft
66'
98'
66'
DIMENSIONS & wEIGHT
INDOOR UNIT
w x H x D
in
39" x 7 7/8" x 25 3/4"
65 3/8" x 9 1/2" x 27 1/2"
32 5/8" x 9 5/8" x 32 5/8"
NET wEIGHT
lbs
62
106
75
SHIPPING wEIGHT
lbs
82
134
97
OUTDOOR UNIT
w x H x D
in
35 3/8" x 32 5/8" x 13"
35 3/8" x 32 5/8" x 13"
35 3/8" x 32 5/8" x 13"
NET wEIGHT
lbs
141
141
141
SHIPPING wEIGHT
lbs
154
154
154
USED wITH:
LENGTH-FT. LIqUID SUCTION
kIT#
S24YF, S36YF 
and C24YF 
systems
15'
3/8”
5/8”
T53150
35'
3/8”
5/8”
T53350