Locked Rotor Voltage (L.R.V.) test 
Locked rotor voltage (L.R.V.) is the actual voltage available 
at the compressor under a stalled condition.
 
Single Phase Connections 
Disconnect power from unit. Using a voltmeter, attach one  
lead of the meter to the run “R” terminal on the compressor 
and the other lead to the common “C” terminal of the com-
pressor. Restore power to unit.
 
Determine L.R.V. 
Start the compressor with the volt meter attached; then  stop 
the unit. Attempt to restart the compressor within a couple 
of seconds and immediately read the voltage on the meter. 
The compressor under these conditions will not start and will 
usually kick out on overload within a few seconds since the 
pressures in the system will not have had time to equalize. 
Voltage should be at or above minimum voltage of 197 VAC, 
as specified on the rating plate. If less than minimum, check 
for cause of inadequate power supply; i.e., incorrect wire 
size, loose electrical connections, etc. 
ComPRESSoR CHECkS 
ELECTRIC SHOCK HAZARD 
WARNING
Turn  off  electric  power  before  service  or 
installation.  Extreme  care  must  be  used,  if  it 
becomes necessary to work on equipment with 
power applied.
 
Failure to do so could result in serious injury or 
death.
Heat generated within the compressor shell, usually due  
to recycling of the motor, is slow to dissipate. It may take  
anywhere from a few minutes to several hours for the  
overload to reset. 
Checking the overload 
 
External overload VPak 9, 12, 18 k Btus 
With power off, remove the leads from compressor termi-
nals. If the compressor is hot, allow the overload to cool 
before starting check. Using an ohmmeter, test continu-
ity across the terminals of the external overload. If you 
do not have continuity; this indicates that the overload is 
open and must be replaced. 
Internal overload VPak 24 k Btus 
The overload is embedded in the motor windings to 
sense the winding temperature and/or current draw. The 
overload is connected in series with the common motor 
terminal.
 
1. With no power to unit, remove the leads from the com-
pressor terminals. Allow motor to cool.
2. Using an ohmmeter, test continuity between terminals 
C-S and C-R. If no continuity, the compressor overload is 
open and the compressor must be replaced.
amperage (L.R.a.) test 
The running amperage of the compressor is the most  impor-
tant of these readings.  A running amperage higher  than that 
indicated in the performance data indicates that  a problem 
exists mechanically or electrically.
 
Single Phase Running and L.R.A. Test 
NOTE: Consult the specification and performance section  
for running amperage. The L.R.A. can also be found on  the 
rating plate.  
 
Select the proper amperage scale and clamp the meter 
probe around the wire to the “C” terminal of the compressor. 
Turn on the unit and read the running amperage on the  me-
ter. If the compressor does not start, the reading will  indicate 
the locked rotor amperage (L.R.A.). 
overloads
The compressor is equipped with an external or internal 
overload  which senses both motor amperage and wind-
ing temperature. High motor temperature or amperage 
heats the overload causing it to open, breaking the com-
mon circuit within the compressor. 
Certain unit components operate at 
temperatures hot enough to cause burns.
Proper safety procedures must be followed, 
and proper protective clothing must be 
worn.
Failure to follow this warning could result 
in moderate to serious injury. 
WARNING
BURN HAZARD 
ELECTRIC SHOCK HAZARD 
WARNING
Turn  off  electric  power  before  service  or 
installation.  Extreme  care  must  be  used,  if  it 
becomes  necessary  to  work  on  equipment 
with power applied.
 
Failure to do so could result in serious injury or 
death.
Internal Overload