Página de 20
SS-GSC13
www.goodmanmfg.com
3
P
roduct
 S
PecificationS
S
peCifiCAtionS
GSC13
0181G*
GSC13
0241F*
GSC13
0301E*
GSC13
0361G*
GSC13
0421C*
GSC13
0481C*
GSC13
0601D*
Cooling Capacities
Tonnage
2
3
4
5
Decibels
76
76
72
75
76
76
77
Compressor
RLA
6.8 
10.8 
13.5 
13.4 
15.4
19.2
21.8
LRA
40
56
68
74
87
112
137
Condenser Fan Motor
Horsepower
1/8
1/8
1/8
1/6
¼
¼
¼
FLA
0.65
0.65
0.7
1.1
1.5
1.5
1.5
Refrigeration System
Refrigerant Line Size
Liquid Line Size (“O.D.)
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
Suction Line Size (“O.D.)
¾"
¾"
¾"
⅞"
1⅛"
1⅛"
1⅛"
Refrigerant Connection Size
Liquid Valve Size (“O.D.)
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
Suction Valve Size (“O.D.) ³
¾"
¾"
¾"
¾" ³
¾" ³
⅞" 4
⅞" 4
Valve Type
Sweat
Sweat
Sweat
Sweat
Sweat
Sweat
Sweat
Refrigerant Charge
87
77
66
77
108
128
118
Electrical Data
AC Volts-Hz
208-230/ 60 208/230-60
208/230-60
208/230-60
208/230-60
208/230-60
208/230-60
Min. Circuit Ampacity¹
9.2
14.2
17.6
17.9
20.8
25.5
28.8
Max. Overcurrent Device²
15
25
30
30
35
40
50
Min / Max Volts
197/253
197/253
197/253
197/253
197/253
197/253
197/253
Electrical Conduit Size
½" or ¾"
½" or ¾"
½" or ¾"
½" or ¾"
½" or ¾"
½" or ¾"
½" or ¾"
Equipment Weight (lbs)
116
116
142
141
141
176
207
Ship Weight (lbs)
130
130
159
159
159
194
225
¹  Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes
²  Must use time-delay fuses or HACR-type circuit breakers of the same size as noted.
³  Installer will need to supply ¾” to ⅞” adapters for suction line connections.
⁴  Installer will need to supply ⅞” to 1⅛” adapters for suction line connections.
Notes
•  Always check the S&R plate for electrical data on the unit being installed.
•  Charge with refrigerant charge listed on S&R plate; 15’ of ⅜” line included in this charge.  
System charge must be adjusted per Installation Instructions Final Charge Procedure.