3.
  
Address Setting
When determining indoor unit addresses with wiring completed without piping
construction
(Manual setting by remote controller)
<Address setting procedure>
Connect a remote controller to the
indoor unit whose address you want to
set one to one.
Turn ON the power.
1
Press 
, and 
 on the R/C
simultaneously for 4 seconds or more.
2
Set code 
 with 
 buttons.
3
Set a refrigerant line address with 
buttons.
4
Press 
 Indication on the LCD shows
normal operation.
5
Set code 
 with 
 buttons.
6
Set indoor unit addresses with 
buttons.
7
Press 
 Indication on the LCD shows
normal operation.
8
Set code 
 with 
 buttons.
9
Set indoor unit addresses with 
buttons as follows:
Individual=
, header unit=
,
follower unit=
10
Press 
 Indication on the LCD shows
normal operation.
11
Press 
.
Indoor unit address setting is completed.
The operation mode returns to normal
OFF.
Group
address
Refrigerant
line address
Indoor unit
address
For systems like this example, connect a wired remote controller
independently without connecting R/C wires, and then set these addresses.
O/U
I/U
O/U
I/U
I/U
I/U
I/U
1
2
2
1
3
2
2
1
2
2
2
2
Wiring example of 2 refrigerant systems
(Solid line: wiring, broken line: refrigerant piping)
(Power cable only)
(Power cable only)
Refrigerant line
address
Indoor unit address
Group address
→ 1
→ 1
→ 1
Group address
2
4
1
5
6
3
7
8
9
10
11
1
2
3
4
8
9
10
11
5
6
7
End
End
Operation procedure
in case of group control
Individual: 0000
Header unit: 0001
Follower unit: 0002
– 
74
 –