– 97 –
RAV-SM561BT-E, RAV-SM801BT-E, RAV-SM1101BT-E, RAV-SM1401BT-E
External view
REQUIREMENT
The hanging bolt pitch on horizontal direction (B) is not halved at center with the ceiling opening size.
Therefore, check the relational position in the following figure.
• Dimension
RAV-SM561BT
RAV-SM801BT
RAV-SM1101, 1401BT
In case of concrete slab
A hole-in-anchor, a hole-in-plug, or a hole-in-bolt is used.
A
B
C
D
E
F
G
H
J
K
M
N
  700
  766
  690
  750
  780
12.7
6.4
252
280
280
1
2
1000
1066
  990
1050
1080
15.9
9.5
252
580
290
2
3
1350
1416
1340
1400
1430
15.9
9.5
252
930
310
2
4
In case of steel structure
Angle is used as it is, or a support angle is newly set.
Hanger bolt
Hanging bolt
Support angle
110
129
44
49
Knock-out hole Ø125 
(Air take-in port)
6-Ø4 Tapping screw undersized 
hole Ø160
Hanging bolt pitch 700 59
41
Main unit dimension 800
75
Hanging bolt pitch B
Main unit dimension A
J = M x K
H
Discharge port flange
N-Ø200
Hanging bolt
4-M10 screw 
(Arranged 
locally)
60~260
9
Suction port 
canvas
(Separate sold)
C
Ceiling open size D
Panel external dimension E
Panel C.L
410
Ceiling open size 470
Panel external dimension 500
Ø26 Power supply, 
remote controller 
cable take-out port
Refrigerant pipe 
connecting port 
(Liquid side ØG)
Suction port 
flange
(Separate sold)
Suction port 
panel
(Separate sold)
Drain pipe connecting port
for vinyl chloride pipe 
(Inner dia. 32, VP. 25)
41
196
393
498
638
50
131
243
50
Refrigerant pipe 
connecting port 
(Gas side ØF)
174
320