Goodman Mfg SS-GSH10C Manual De Usuario

Descargar
Página de 12
p
RoduCt
 S
pECifiCationS
p
RoduCt
 S
pECifiCationS
10
www.goodmanmfg.com
SS-GSH10C
E
xpandEd
 H
EatinG
 d
ata
GSH100903A* / AR090
Outdoor Ambient Temperature
65°F
60°F
55°F
50°F
47°F
45°F
40°F
35°F
30°F
25°F
20°F
17°F
15°F
10°F
5°F
0°F
-5°F
-10°F
MBh
103.1
97.6
91.8
85.9
82.0
79.5
73.8
68.1
66.0
61.0
56.1
53.0
51.0
45.8
40.6
35.4
30.2
24.8
∆T
33.1
31.4
29.5
27.6
26.4
25.5
23.7
21.9
21.2
19.6
18.0
17.0
16.4
14.7
13.1
11.4
9.7
8.0
kW
8.04
7.89
7.74
7.59
7.50
7.44
7.29
7.14
7.48
7.32
7.16
7.06
7.00
6.83
6.67
6.51
6.34
6.18
Amps
24.4
22.6
21.1
19.8
19.1
18.7
17.6
16.7
16.0
15.3
14.5
14.2
14.0
13.3
12.4
11.6
10.7
9.6
COP
3.75
3.62
3.47
3.31
3.20
3.13
2.96
2.79
2.58
2.44
2.30
2.20
2.14
1.96
1.78
1.59
1.39
1.17
EER
12.8
12.4
11.9
11.3
10.9
10.7
10.1
9.5
8.8
8.3
7.8
7.5
7.3
6.7
6.1
5.4
4.8
4.0
Hi PR
244
234
225
215
210
206
198
190
182
174
167
163
160
154
148
142
137
132
Lo PR
72
66
62
57
54
52
48
43
38
34
30
28
27
23
20
17
15
11
GSH100903B* / AR090
Outdoor Ambient Temperature
65°F
60°F
55°F
50°F
47°F
45°F
40°F
35°F
30°F
25°F
20°F
17°F
15°F
10°F
5°F
0°F
-5°F
-10°F
MBh
105.8 100.1
94.2
88.1
84.1
81.5
75.7
69.8
64.1
59.1
54.5
51.4
49.5
44.4
39.4
34.3
29.3
24.0
∆T
32.1
30.4
28.6
26.7
25.5
24.8
23.0
21.2
19.5
18.0
16.5
15.6
15.0
13.5
12.0
10.4
8.9
7.3
kW
8.03
7.88
7.73
7.58
7.49
7.42
7.28
7.12
7.95
7.77
7.59
7.49
7.42
7.24
7.06
6.88
6.70
6.52
Amps
30.2
28.1
26.4
24.9
24.1
23.7
22.4
21.4
20.5
19.7
18.8
18.4
18.2
17.4
16.3
15.5
14.4
13.2
COP
3.85
3.72
3.57
3.40
3.29
3.21
3.05
2.87
2.36
2.23
2.10
2.01
1.95
1.80
1.63
1.46
1.28
1.08
EER
13.2
12.7
12.2
11.6
11.2
11.0
10.4
9.8
8.1
7.6
7.2
6.9
6.7
6.1
5.6
5.0
4.4
3.7
Hi PR
268
257
247
236
230
226
217
209
200
191
183
179
176
169
162
156
150
145
Lo PR
72
67
63
57
54
52
48
43
39
34
30
28
27
23
20
17
15
11
GSH101203A* / AR120
Outdoor Ambient Temperature
65°F
60°F
55°F
50°F
47°F
45°F
40°F
35°F
30°F
25°F
20°F
17°F
15°F
10°F
5°F
0°F
-5°F
-10°F
MBh
132.6 125.5 118.2 110.5 105.5 102.2
95.0
87.6
85.4
78.8
72.5
68.5
66.0
59.2
52.5
45.8
39.0
32.0
∆T
30.7
29.1
27.4
25.6
24.4
23.7
22.0
20.3
19.8
18.2
16.8
15.9
15.3
13.7
12.1
10.6
9.0
7.4
kW
10.41 10.21 10.01
9.81
9.70
9.62
9.43
9.23
9.69
9.47
9.26
9.13
9.05
8.83
8.62
8.41
8.19
7.98
Amps
28.3
26.2
24.5
23.0
22.1
21.7
20.4
19.3
18.4
17.6
16.7
16.3
16.1
15.2
14.1
13.3
12.2
10.9
COP
3.73
3.60
3.45
3.29
3.18
3.11
2.95
2.78
2.58
2.44
2.29
2.20
2.13
1.96
1.78
1.59
1.40
1.17
EER
12.7
12.3
11.8
11.3
10.9
10.6
10.1
9.5
8.8
8.3
7.8
7.5
7.3
6.7
6.1
5.4
4.8
4.0
Hi PR
221
212
203
195
190
186
179
172
165
157
151
147
145
139
134
128
124
120
Lo PR
66
62
58
53
50
48
44
39
36
32
28
26
25
21
18
15
13
11
High pressure is measured at the suction service valve ( the larger valve).
Amps = Outdoor unit amps (comp.+fan)
Low pressure is measured at the gauge port connection.
kW = Total system power
Calculations are based on nominal CFM and 70 °F indoor dry bulb.