York YPAL 051 Manual De Usuario

Descargar
Página de 168
151
JOHNSON CONTROLS
FORM 100.50-NOM6 (1207)
7
MENU ITEM
DEFINITION
SPACE SENSOR DETECTED
IDENTIFIES IF THE UNIT CONTROLLER HAS DETECTED THE 
PRESENCE OF A SPACE SENSOR.  IF THE UNIT CONTROLLER 
DETECTS A SPACE SENSOR IT WILL SELF CONFIGURE TO USE 
IT FOR CONTROL OF THE UNIT.
SPACE SENSOR FAULT OVERRIDE ENABLE
WHEN THIS OPTION IS TURNED ON THE CONTROLLER USES 
THE RETURN AIR TEMPERATURE INPUT IN PLACE OF THE 
SPACE TEMPERATURE INPUT TO CONTROL THE UNIT.  TURING 
THIS OPTION ON ALLOWS THE UNIT TO OPERATE IN A VAV 
STAND ALONE MODE
SPACE TEMP
THIS PARAMETER GIVES THE CURRENT VALUE OF THE SPACE 
TEMPERATURE INPUT
SPACE TEMP TRENDING ALARM TEMP
TO ENABLE THIS FEATURE THE PARAMETER MUST BE SET 
TO OTHER THEN 0.  A VALUE OTHER THEN 0 IS THE NUMBER 
OF DEGREES ABOVE OR BELOW THE SETPOINT THE 
TEMPERATURE MUST BE TO START THE TIMING
SPACE TEMP TRENDING ALARM TIME
THIS PARAMETER ESTABLISHED THE AMOUNT OF TIME THE 
SPACE TEMPERATURE MUST BE TRENDING ABOVE OR BELOW 
THE SPACE TEMP TRENDING ALARM TEMP BEFORE THE ALARM 
WILL BE INITIATED.
SPACE TEMPERATURE OFFSET RANGE
THIS SETPOINT ESTABLISHES THE MAXIMUM AMOUNT OF 
HEATING OR COOLING RESET AVAILABLE THROUGH THE 
RESET FEATURE ON A SPACE SENSOR.
STAGES OF HEAT AVAILABLE
THIS PARAMETER IDENTIFIES THE NUMBER OF STAGES OF 
HEAT THE UNIT CONTROLLER IS SET UP TO CONTROL
STATE COMPRESSOR OFF - LOW SUPPLY 
VOLTAGE
THIS IDENTIFIES THE COMPRESSORS ARE OFF BECAUSE OF 
LOW SUPPLY VOLTAGE.  ON WHEN THIS STATE IS ACTIVE
STATE COMPRESSORS OFF - LOW AMBIENT 
TEMPERATURE
THIS IDENTIFIES THE COMPRESSOR ARE OFF BECAUSE 
THE OUTDOOR TEMPERATURE IS BELOW THE LOW AMBIENT 
LOCKOUT TEMPERATURE.  ON WHEN THIS STATE IS ACTIVE
STATUS COMPRESSOR OFF - ECON IS USING 
FREE COOLING
THIS IDENTIFIES THE COMPRESSORS ARE OFF BECAUSE THE 
UNIT CONTROLLER IS USING OUTDOOR AIR FOR COOLING.  ON 
WHEN THIS IS ACTIVE
SUPPLY AIR TEMP
THIS PARAMETER GIVES THE CURRENT VALUE FOR THE 
SUPPLY AIR TEMPERATURE INPUT
SUPPLY AIR TEMP ALARM SETPOINT FOR 
COOLING
TO ENABLE THIS FEATURE THE PARAMETER MUST BE SET TO 
OTHER THEN 0.  A VALUE OTHER THEN 0 ESTABLISHES THE 
SETPOINT TO USE IN DETERMINE WHEN TO INITIATE A SUPPLY 
AIR TEMP ALARM FOR COOLING
SUPPLY AIR TEMP ALARM SETPOINT FOR 
HEATING
TO ENABLE THIS FEATURE THE PARAMETER MUST BE SET TO 
OTHER THEN 0.  A VALUE OTHER THEN 0 ESTABLISHES THE 
SETPOINT TO USE IN DETERMINE WHEN TO INITIATE A SUPPLY 
AIR TEMP ALARM FOR HEATING
SUPPLY AIR TEMP LIMIT COOLING SETPOINT
THIS SET POINT IS USED BY THE UNIT CONTROLLER DURING 
ECONOMIZER LOADING OR SUPPLY AIR TEMP LIMIT MODE OF 
OPERATION
TABLE 7-1 – DEFINITIONS (CONTINUED)
Continued on next page