SEQUENCE OF OPERATION
YCW With a Chilled Water Coil
The unit will respond to a cooling command from 
the  thermostat  by  powering  a  water  control  valve 
open. The fan will operate at the speed selected at the 
thermostat. When the space reaches the temperature 
setpoint at the thermostat, the cooling valve will close 
and the fan will continue to operate.
When using the T420 manual C/O thermostat and the 
TB3-3/TB2-5 jumper is in place, the fan will con-
tinue to operate at the fan speed selected. Removing 
the jumper will cause the fan to shut down when the 
thermostat is satisfied.
When using the T200 thermostat, the stat will auto-
matically regulate the fan speed based on the differ-
ence between the space temp and setpoint - 
@
 4˚F off 
setpoint, the fan will run 
@
 HI; 
@
 3˚F off setpoint, the 
fan will run 
@
 MED; 
@
 2˚F off setpoint, the fan will 
run 
@
 LO. When the thermostat is satisfied, the water 
valve will be deenergized and the fan will revert to 
LO speed.
The YCW-HW with Both a Chilled Water Coil and a 
Hot Water Coil. 
The unit control thermostat, on a call for heating, will 
energize the hot water control valve. When the ther-
mostat is set for cooling, it will energize the chilled 
water valve on a call for cooling. The fan will operate 
at the speed selected at the thermostat. When the space 
reaches the temperature setpoint at the thermostat, the 
cooling valve will close (on cooling) or the heating 
valve will close (on heating) and the fan will continue 
to operate.
When using the T420 manual C/O thermostat and the 
TB3-3/TB2-5 jumper is in place, the fan will con-
tinue to operate at the fan speed selected. Removing 
the jumper will cause the fan to shut down when the 
thermostat is satisfied.
When using the T421 auto C/O thermostat and the 
TB3-3/TB2-5 jumper is in place, the fan will con-
tinue to operate at the fan speed selected. Removing 
the jumper will cause the fan to shut down when the 
thermostat is satisfied.
When using the T200 thermostat, the stat will auto-
matically regulate the fan speed based on the differ-
ence between the space temp and setpoint - 
@
 4˚F off 
setpoint, the fan will run 
@
 HI; 
@
 3˚F off setpoint, the 
fan will run 
@
 MED; 
@
 2˚F off setpoint, the fan will 
run 
@
 LO. When the thermostat is satisfied, the water 
valve will be deenergized and the fan will revert to 
LO speed.
The  YCWE  With  Both  a  Chilled  Water  Coil  and 
Electric Heating Coil. 
The unit control thermostat, on a call for heating, will 
energize the heater contactor(s). When the thermostat 
is set for cooling, it will energize the chilled water 
valve on a call for cooling. The fan will operate at 
the speed selected at the thermostat. When the space 
reaches the temperature setpoint at the thermostat, 
the cooling valve will close (on cooling) or the heat-
ing contactors will open (on heating) and the fan will 
continue to operate.
When using the T420 manual C/O thermostat and the 
TB3-3/TB2-5 jumper is in place, the fan will con-
tinue to operate at the fan speed selected. Removing 
the jumper will cause the fan to shut down when the 
thermostat is satisfied.
When using the T421 auto C/O thermostat and the 
TB3-3/TB2-5 jumper is in place, the fan will con-
tinue to operate at the fan speed selected. Removing 
the jumper will cause the fan to shut down when the 
thermostat is satisfied.
When using the T200 thermostat, the stat will auto-
matically regulate the fan speed based on the differ-
ence between the space temp and setpoint - 
@
 4˚F off 
setpoint, the fan will run 
@
 HI; 
@
 3˚F off setpoint, the 
fan will run 
@
 MED; 
@
 2˚F off setpoint, the fan will 
run 
@
 LO. When the thermostat is satisfied, the water 
valve will be deenergized (on cooling) or the heating 
contactor will open (on heating) and the fan will revert 
to LO speed.