York D3CE Manual De Usuario

Descargar
Página de 20
COOLING CAPACITIES (CFM Air Flow) -
 180 UNITS
Air On
Evaporator Coil
Total
Cap.
1
MBH
Power
Input
2
kW
Sensible Capacity
1
, MBH
Entering Dry Bulb Temp., 
°
F
CFM
WB 
°
F
90
86
82
79
75
72
@80
°
F Air Temperature on Condenser Coil1
7200
73
227
14.7
175
151
126
102
78
-
70
213
14.4
200
176
152
127
103
79
66
199
14.0
199
199
177
153
128
104
63
193
14.0
193
193
190
166
142
117
59
188
13.9
188
188
188
176
152
128
5930
73
210
14.5
157
136
115
93
72
-
70
197
14.2
180
159
138
116
95
74
66
184
13.9
184
182
160
139
118
97
63
179
13.8
179
179
172
151
130
109
59
174
13.7
174
174
174
163
142
121
4450
73
195
14.3
127
111
95
79
63
-
70
183
14.0
146
130
114
98
82
66
66
171
13.6
165
149
133
117
101
86
63
166
13.6
166
159
143
127
111
96
59
162
13.5
162
162
153
137
121
105
@95
°
F Air Temperature on Condenser Coil
7200
73
207
15.9
170
146
122
98
74
-
70
195
15.5
195
171
147
123
99
75
66
183
15.2
183
183
172
148
124
100
63
179
15.1
179
179
179
159
135
111
59
174
15.0
174
174
174
162
138
113
5930
73
192
15.9
150
129
108
87
66
-
70
181
15.6
172
151
130
109
88
67
66
170
15.2
170
170
153
132
110
89
63
166
15.1
166
166
162
141
120
99
59
161
15.0
161
161
161
151
130
109
4450
73
177
15.6
123
107
91
75
59
-
70
167
15.3
142
126
110
94
78
62
66
157
14.9
157
145
129
113
97
81
63
153
14.8
153
153
137
121
105
89
59
149
14.7
149
149
145
129
113
97
@115
°
F Air Temperature on Condenser Coil
7200
73
169
18.2
157
133
109
85
61
-
70
161
17.6
161
158
134
110
85
61
66
154
17.1
154
154
154
135
110
86
63
149
17.1
149
149
149
137
112
88
59
144
17.1
144
144
144
132
107
83
5930
73
169
17.8
141
120
99
78
57
-
70
161
17.2
161
142
121
100
79
58
66
153
16.6
153
153
144
123
102
81
63
148
16.6
148
148
148
128
107
86
59
143
16.6
143
143
143
133
112
90
4450
73
159
17.5
114
98
82
66
50
-
70
151
17.0
133
117
101
85
69
53
66
144
16.4
144
136
120
104
88
72
63
139
16.4
139
139
124
108
92
76
59
135
16.4
135
135
128
112
96
80
1
These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor. Refer to the appropriate Blower Performance Table for the kW of the
  supply air blower motor.
2
These ratings include the condenser fan motors (Total 2.3 kW) and the compressor motors but not the supply air blower motor.
530.26-TG3YI
Unitary Products Group
5