York Y33 Manual De Usuario

Descargar
Página de 96
246653-YTG-E-0108
Johnson Controls Unitary Products
59
TABLE 44: POWER EXHAUST - TWO FORWARD CURVED FANS - 30 & 40 TON
1
A
IRFLOW
 CFM
A
VAILABLE
 E
XTERNAL
 S
TATIC
 P
RESSURE
 (IWG)
0.2
0.4
.06
0.8
1.0
RPM
BHP
2
 
3
RPM
BHP
2 3
RPM
BHP
2 3
RPM
BHP
2 3
RPM
BHP
2 3
4000
363
0.32
468
0.53
560
0.74
641
0.95
716
1.16
5000
402
0.53
494
0.74
576
1.05
652
1.26
722
1.47
6000
445
0.84
527
1.05
602
1.37
670
1.68
735
2.00
7000
494
1.26
565
1.58
633
1.79
697
2.10
757
2.52
8000
544
1.79
609
2.10
670
2.42
729
2.73
784
3.15
9000
597
2.42
654
2.84
711
3.15
765
3.47
817
3.89
10000
651
3.26
703
3.68
754
3.99
805
4.41
853
4.83
11000
705
4.31
753
4.73
801
5.15
847
5.57
893
5.99
12000
761
5.46
805
5.88
849
6.30
893
6.83
934
7.25
13000
817
6.93
858
7.35
899
7.77
939
8.30
979
8.82
14000
874
8.51
912
9.03
950
9.56
988
9.98
1025
10.50
15000
932
10.40
967
10.92
1002
11.55
1037
12.08
1072
12.60
16000
989
12.60
1022
13.23
1055
13.76
1088
14.28
-
-
A
IRFLOW
 CFM
A
VAILABLE
 E
XTERNAL
 S
TATIC
 P
RESSURE
 (IWG)
1.2
1.4
1.6
1.8
2
RPM
BHP
2 3
RPM
BHP
2 3
RPM
BHP
2 3
RPM
BHP
2 3
RPM
BHP
2 3
4000
783
1.47
844
1.68
903
1.89
956
2.21
1008
2.42
5000
788
1.79
848
2.10
906
2.42
959
2.63
1011
2.94
6000
798
2.21
855
2.63
911
2.94
963
3.26
1014
3.57
7000
814
2.84
869
3.15
922
3.47
972
3.89
1021
4.20
8000
837
3.47
889
3.89
938
4.20
987
4.62
1033
5.04
9000
866
4.31
915
4.73
961
5.15
1007
5.57
1050
5.99
10000
900
5.25
945
5.67
989
6.20
1032
6.62
1073
7.14
11000
936
6.41
979
6.93
1020
7.35
1061
7.88
1101
8.30
12000
976
7.77
1016
8.30
1055
8.72
1094
9.24
1131
9.77
13000
1018
9.35
1055
9.87
1093
10.40
1129
10.92
1165
11.55
14000
1061
11.13
1098
11.66
1133
12.29
1167
12.92
1202
13.44
15000
1107
13.23
1141
13.76
1175
14.39
1208
14.91
1240
15.54
1.
Fan performance is based on system/cabinet effects and back draft damper effects at standard air density and 0 feet elevation.
2.
BHP includes the sum of both exhaust fan motors.
3.
BHP does includes 5% drive losses.