American Power Conversion DX Manual De Usuario

Descargar
Página de 96
77
NetworkAIR FM DX 60 Hz Operation, Maintenance, and Troubleshooting
Compressor noisy
• Compressor or compressors may 
be rotating in the wrong direction
• Liquid slugging
• High head pressure
• Verify the pressure differential across the 
suction and discharge for each compressor. If 
no differential is present, verify the correct 
phasing to each compressor.
• Check for low evaporator superheat.
• Check operation of crankcase heaters.
• Verify liquid line solenoid valves close tightly 
during the off cycle. Check for obstructions 
which may prevent the valve from closing.
• Check operating head pressure.
Controls erratic or 
inoperative
• Control transformer problem
• Loose or broken wiring
• Module configured incorrectly
• System is in alarm
• Check control transformers for proper input 
voltage.
• Check control transformer secondary voltage. 
Output should be within + or - 10% of rated 
output.
• Check wiring for loose or broken connections.
• Set module configuration according to 
nameplate and options selected.
• Check front panel display for active system 
alarm.
Evaporator coil ices
• Dirty or blocked evaporator coil
• Dirty or blocked air filters
• Low  airflow
• Low evaporator superheat
• Low return air temperature
• Low refrigerant charge
• Clean evaporator coil.
• Check filters and replace as needed.
• Check for correct airflow setting.
• Check superhear and adjust to 10-15
°
F.
• Verify the return air temperature is not below 
20ºC (68
°
F).
• Check for short cycling of cold supply air.
• Check subcooling and ensure it is at least 
10-15
°
F. Repair leak and recharge system.
Head pressure too 
high
• Air cooled condenser malfunction
• Condenser water regulating valve 
malfunction
• Overcharge of refrigerant
• Non-condensable in system
• Fluid cooler malfunction
• Fluid pump malfunction
• Low fluid flow
• Glycol concentration higher than 
40%
• Check and clean the condenser coil. Check 
condenser fan operation and settings.
• Check water regulating valve, actuator, and 
linkage for proper operation.
• Remove excess refrigerant from system.
• Recover refrigerant charge, evacuate system 
and recharge.
• Check and clean the fluid cooler coil. Check 
fluid cooler fan operation.
• Check pump operation.
• For water cooled systems, check the condenser 
water flow rate and water supply temperature. 
Check pressure drop across the heat 
exchanger. Check and clean field installed 
strainers.
• For glycol cooled systems, check the water 
flow rate and water supply temperature. Check 
pressure drop across the heat exchanger. 
Check and clean field installed strainers.
• Verify glycol concentration, reduce to 
maximum 40%.
Problem
Possible Cause
Corrective Action