American Power Conversion DX Manual De Usuario
77
NetworkAIR FM DX 60 Hz Operation, Maintenance, and Troubleshooting
Compressor noisy
• Compressor or compressors may
be rotating in the wrong direction
• Liquid slugging
• High head pressure
• Verify the pressure differential across the
suction and discharge for each compressor. If
no differential is present, verify the correct
phasing to each compressor.
no differential is present, verify the correct
phasing to each compressor.
• Check for low evaporator superheat.
• Check operation of crankcase heaters.
• Verify liquid line solenoid valves close tightly
• Check operation of crankcase heaters.
• Verify liquid line solenoid valves close tightly
during the off cycle. Check for obstructions
which may prevent the valve from closing.
which may prevent the valve from closing.
• Check operating head pressure.
Controls erratic or
inoperative
inoperative
• Control transformer problem
• Loose or broken wiring
• Module configured incorrectly
• Module configured incorrectly
• System is in alarm
• Check control transformers for proper input
voltage.
• Check control transformer secondary voltage.
Output should be within + or - 10% of rated
output.
output.
• Check wiring for loose or broken connections.
• Set module configuration according to
• Set module configuration according to
nameplate and options selected.
• Check front panel display for active system
alarm.
Evaporator coil ices
• Dirty or blocked evaporator coil
• Dirty or blocked air filters
• Low airflow
• Low evaporator superheat
• Low return air temperature
• Dirty or blocked air filters
• Low airflow
• Low evaporator superheat
• Low return air temperature
• Low refrigerant charge
• Clean evaporator coil.
• Check filters and replace as needed.
• Check for correct airflow setting.
• Check superhear and adjust to 10-15
• Check filters and replace as needed.
• Check for correct airflow setting.
• Check superhear and adjust to 10-15
°
F.
• Verify the return air temperature is not below
20ºC (68
°
F).
• Check for short cycling of cold supply air.
• Check subcooling and ensure it is at least
• Check subcooling and ensure it is at least
10-15
°
F. Repair leak and recharge system.
Head pressure too
high
high
• Air cooled condenser malfunction
• Condenser water regulating valve
malfunction
• Overcharge of refrigerant
• Non-condensable in system
• Non-condensable in system
• Fluid cooler malfunction
• Fluid pump malfunction
• Low fluid flow
• Low fluid flow
• Glycol concentration higher than
40%
• Check and clean the condenser coil. Check
condenser fan operation and settings.
• Check water regulating valve, actuator, and
linkage for proper operation.
• Remove excess refrigerant from system.
• Recover refrigerant charge, evacuate system
• Recover refrigerant charge, evacuate system
and recharge.
• Check and clean the fluid cooler coil. Check
fluid cooler fan operation.
• Check pump operation.
• For water cooled systems, check the condenser
• For water cooled systems, check the condenser
water flow rate and water supply temperature.
Check pressure drop across the heat
exchanger. Check and clean field installed
strainers.
Check pressure drop across the heat
exchanger. Check and clean field installed
strainers.
• For glycol cooled systems, check the water
flow rate and water supply temperature. Check
pressure drop across the heat exchanger.
Check and clean field installed strainers.
pressure drop across the heat exchanger.
Check and clean field installed strainers.
• Verify glycol concentration, reduce to
maximum 40%.
Problem
Possible Cause
Corrective Action