InRoom SC 50 Hz User Guide
8
Installation
Location
Requirements 
Dimensions are shown in mm (in).
> 500 (20)
> 500 (20)
na3362b
MODE
InRoo
m SC
TEMP
When deciding where to locate the cooling 
unit, consider cooling needs, air flow, and 
the location of the electrical outlet. The 
cooling unit can be no more than 2.4 m 
 
(8 ft) from the electrical outlet.
Cooling needs. 
Position the cooling unit 
as close as possible to the main heat source 
that requires cooling.
Air flow. 
Position the cooling unit at least 
500 mm (20 in) away from a wall or other 
equipment on any side to avoid impeding 
air flow.
Location of electrical outlet. 
Place the 
cooling unit no farther than 2.4 m (8 ft) 
from a dedicated 220-240V, 50Hz, 15A 
branch circuit receptacle. 
Electrical Hazard: Do not use extension cords with this equipment. Using an extension 
cord reduces circuit protection and will void the warranty. 
The cooling unit shall be installed in accordance with national wiring regulations.
The cooling unit shall not be installed in a laundry room.
Caution: To help avoid loss of cooling, only connect this equipment to a single-outlet 
dedicated circuit.