PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566D240
LEGEND
566D240/524A-C300 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
7,500
10,000
12,500
Evaporator Air — Ewb (F)
57
62
67
72
57
62
67
72
57
62
67
72
80
TC
244.0
249.0
268.0
291.0
264.0
264.0
279.0
301.0
278.0
278.0
286.0
307.0
SHC
244.0
233.0
194.0
152.0
264.0
264.0
224.0
171.0
278.0
278.0
252.0
189.0
kW
18.90
19.20
19.90
20.80
19.70
19.70
20.30
21.20
20.30
20.30
20.60
21.40
85
TC
239.0
244.0
263.0
284.0
259.0
259.0
273.0
294.0
272.0
272.0
280.0
300.0
SHC
239.0
231.0
192.0
150.0
259.0
259.0
222.0
169.0
272.0
272.0
249.0
187.0
kW
19.70
19.90
20.70
21.60
20.50
20.50
21.10
22.00
21.10
21.10
21.40
22.30
95
TC
230.0
233.0
251.0
272.0
249.0
249.0
260.0
281.0
261.0
261.0
267.0
286.0
SHC
230.0
225.0
187.0
146.0
249.0
249.0
217.0
164.0
261.0
261.0
243.0
182.0
kW
21.30
21.40
22.20
23.20
22.10
22.10
22.70
23.70
22.70
22.70
23.00
23.90
100
TC
226.0
228.0
245.0
265.0
244.0
244.0
254.0
274.0
256.0
256.0
260.0
279.0
SHC
226.0
222.0
184.0
143.0
244.0
244.0
214.0
162.0
256.0
256.0
240.0
180.0
kW
22.00
22.10
23.00
24.00
22.90
22.90
23.50
24.50
23.60
23.60
23.80
24.80
105
TC
221.0
222.0
239.0
259.0
238.0
238.0
247.0
267.0
250.0
250.0
254.0
272.0
SHC
221.0
219.0
182.0
141.0
238.0
238.0
212.0
160.0
250.0
250.0
237.0
177.0
kW
22.80
22.80
23.70
24.80
23.70
23.70
24.20
25.30
24.40
24.40
24.60
25.60
115
TC
212.0
212.0
226.0
245.0
227.0
227.0
235.0
253.0
238.0
238.0
240.0
257.0
SHC
212.0
211.0
177.0
136.0
227.0
227.0
206.0
155.0
238.0
238.0
231.0
172.0
kW
24.30
24.30
25.20
26.40
25.30
25.30
25.80
26.90
26.00
26.00
26.10
27.20
566D240/524A-B300 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
7,500
10,000
12,500
Evaporator Air — Ewb (F)
57
62
67
72
57
62
67
72
57
62
67
72
80
TC
230.0
236.0
255.0
277.0
249.0
249.0
266.0
287.0
262.0
262.0
272.0
293.0
SHC
230.0
219.0
183.0
144.0
249.0
248.0
209.0
161.0
262.0
262.0
233.0
176.0
kW
18.40
18.60
19.40
20.20
19.10
19.20
19.80
20.60
19.60
19.60
20.10
20.90
85
TC
226.0
231.0
250.0
271.0
244.0
244.0
259.0
281.0
256.0
256.0
266.0
287.0
SHC
226.0
217.0
181.0
142.0
244.0
244.0
207.0
159.0
256.0
256.0
231.0
174.0
kW
19.20
19.40
20.20
21.00
19.90
19.90
20.60
21.50
20.40
20.40
20.80
21.70
95
TC
218.0
221.0
239.0
259.0
235.0
235.0
248.0
268.0
246.0
246.0
254.0
273.0
SHC
218.0
211.0
176.0
138.0
235.0
235.0
203.0
154.0
246.0
246.0
226.0
169.0
kW
20.60
20.80
21.70
22.60
21.50
21.50
22.10
23.10
22.00
22.00
22.40
23.30
100
TC
214.0
217.0
233.0
253.0
230.0
230.0
242.0
261.0
241.0
241.0
248.0
266.0
SHC
214.0
208.0
174.0
136.0
230.0
230.0
200.0
152.0
241.0
241.0
223.0
167.0
kW
21.40
21.50
22.40
23.40
22.20
22.20
22.90
23.80
22.80
22.80
23.20
24.10
105
TC
209.0
212.0
228.0
247.0
225.0
225.0
236.0
255.0
236.0
236.0
242.0
260.0
SHC
209.0
206.0
172.0
133.0
225.0
225.0
198.0
150.0
236.0
236.0
220.0
165.0
kW
22.10
22.20
23.10
24.20
23.00
23.00
23.60
24.60
23.60
23.60
23.90
24.90
115
TC
201.0
202.0
216.0
235.0
215.0
215.0
224.0
242.0
226.0
226.0
229.0
246.0
SHC
201.0
199.0
167.0
129.0
215.0
215.0
193.0
145.0
226.0
226.0
214.0
160.0
kW
23.60
23.70
24.60
25.80
24.60
24.50
25.10
26.20
25.20
25.20
25.40
26.50
Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW
— Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC
— Total Capacity (1000 Btuh) Gross
5
0TF
Q00
4
-012
56
6D
/E1
50-
24